The RTU is powered at low voltage (12VDC 160mA), preferably using a
power supply module with battery backup (RTU-Qxx), or using an ordinary
power supply having the same characteristics. The power cables must be
dimensioned as indicated in the table below. The maximum allowable voltage
drop on the power cable is 1V.
• Cable length(m) = 1V / (I[A] load x 2 x (res [Ohm/km] /1000))
Cabl e Type
AW G
m m 2
12
3. 3
14
2
16
1. 3
18
0. 9
20
0. 6
22
0. 35
24
0. 2
The device is equipped with 2 non-removable cables of 2m length:
• Two-pole, twisted, unpolarized cable dedicated to the LON line
connection
- LON a
- LON b
• Ten-pole cable, providing the following signals:
- +12VDC
- GND
- INPUT 1 +
- INPUT 2 +
- RELAY 2 contact C
- RELAY 2 contact NC
- RELAY 2 contact NO
- RELAY 1 contact C
- RELAY 1 contact NC
- RELAY 1 contact NO
The signals must be connected using a shunt box with IP protection level
in conformance with the type of environment in which it is to be used:
- IP55 for moist environments
- Recessed box or IP31 at least for inside installations
The shunt box must be positioned within the perimeter controlled by the
access control system.
o
n
n
e
c
t
i
o
n
s
o
n
n
e
c
t
i
o
n
s
Ext ensi on [ m ] based on l oad
ohm / Km 160 [ m A] 320 [ m A]
5. 7
548
8. 8
355
14
223
21
149
34
92
52
60
85
37
0,325 mm
0,325 mm
0,34 mm
0,34 mm
0,22 mm
0,22 mm
0,22 mm
0,22 mm
0,22 mm
0,56 mm
0,56 mm
0,56 mm
Page 4 of 24
274
178
112
74
46
30
18
2
white
2
orange
2
red
2
black
2
green / white
2
gray / green
2
brown
2
white
2
blue
2
green
2
yellow
2
gray