Refrigeration Cycle Diagram

• LV-B1861CL
• LV-B1864CL
• LV-B2461CL
• LV-B2464CL
INDOOR UNIT
HEAT
EXCHANGER
(EVAPORATOR)
MODEL
LV-B1861CL
LV-B1864CL
LV-B2461CL
LV-B2464CL
For installation over rated distance, 30g of refrigerant should be added for each meter.
ex) When installed at a distance of 15m, 300g of refrigerant should be added.
(15-5) x 30g = 300g
LIQUID SIDE
GAS SIDE
Pipe size(Diameter: )
Gas
Liquid
1/2"
1/4"
1/2"
1/4"
5/8"
1/4"
5/8"
1/4"
–9–
OUTDOOR UNIT
CAPILLARY TUBE
HEAT
EXCHANGER
(CONDENSER)
COMPRESSOR
Piping length(m)
Rated
Max
5
15
5
15
5
20
5
20
Elevation(m)
Rated
Max
5
8
5
8
5
8
5
8