Example Of Output Relay Programming - ADEMCO VIA-30Pse Installation Instructions Manual

Hide thumbs Also See for VIA-30Pse:
Table of Contents

Advertisement

If a zone type or system operation will be used to START the relay action,
02 Start:
Zn Typ
enter the appropriate two-digit code (see table that follows). If not, enter 00.
Not Used
00
Press the [ ] key to continue.
00 = Not Used
01 = Entry/Exit
03 = Perimeter
04 = Interior Follower
20 = Arming–Stay
21 = Arming–Away
22 = Disarming (Code + OFF) 35 = Code + # + 8 Key Entry
31 = End of Exit Time
32 = Start of Entry Time
If a zone list will be used to STOP, or restore, the relay action, enter the zone list
02 Stop:
Zn List
(ZL) number 1, 2, or 3 (to be programmed in 81 mode). If not used, enter 0.
No List
0
Press the [ ] key to continue.
If a zone type or system operation will be used to STOP the relay action, enter
02 Stop:
Zn Typ
the appropriate two digit code (see the "ZT" choices listed above). If not, enter
Not Used
00
00. Press the [ ] key to continue.
This screen again displays a summary of the current relay START
02
A EV ZL ZT
programming.
STT 0
0
0
00
Press the [ ] key to continue.
This screen again displays a summary of the current relay STOP programming.
02
A EV ZL ZT
Press the [ ] key to continue.
STP – –
0
00
The display then returns again to the first screen so that the next relay number
to be programmed can be entered, or enter [0][0] to end relay programming.
Previously entered data can be reviewed by pressing [#] [8] [0]. After the
relay number is chosen, press [ ] to go to the next screens. This is a review
mode only, and data cannot be changed.
Example of
A lamp is to be turned on when any one of 3 specific zones are faulted or
Output Relay
when any 24-hour auxiliary zone is disturbed. We want to turn off the
Programming
lamp manually without affecting the arming status of the system.
In field *80 we choose Output Relay 01 and program the Action (A) to be "2"
(Close and stay closed). The Event we are looking for to start the relay action
is a fault, so we will program "2" in (EV). We will use Zone List 1 for the 3
specific zones, so will program "1" in (ZL), (and will program these 3 zones in
field *81's Zone List 1).
The second condition for turning on the indicator is triggering a 24 hour aux.
zone (Zone Type 08), so we will program (ZT) as "08".
To stop relay action and turn off the indicator, we do not want to use a restore
of any zone, so we will program a "0" for the " Restore of" Zone List (ZL). To
choose a manual entry of User Code + [#] + [7] to turn it off, we will program
(ZT) as "34".
If no other relay is to be programmed, go to field *81 and program the 3
specific zones in Zone List 1.
CHOICES FOR ZONE TYPES
05 = Trouble Day/Alarm Night 08 = 24 Hr Aux
06 = 24 Hr Silent
07 = 24 Hr Audible
CHOICES FOR SYSTEM OPERATION
33 = Any Burglary Alarm
34 = Code + # + 7 Key Entry
36 = At Bell Timeout**
38 = Chime
**Or at Disarming, whichever occurs earlier.
7 –5
09 = Fire
10 = Interior w/Delay
39 = Any Fire Alarm
40 = Bypassing
41 = AC Power Failure
42 = System Batt. Low
58 = Duress