6.
CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DEFFERENCE
INDOOR UNIT: 7000BTU (AOU18RLXFZ)
COOLING
1
Indoor unit is
upper than
outdoor unit.
Height
difference
H
2
Indoor unit is
under than
outdoor unit
HEATING
1
Indoor unit is
upper than
outdoor unit.
Height
difference
H
2
Indoor unit is
under than
outdoor unit
Indoor unit
Connection pipe
1 Indoor unit is upper than outdoor unit.
5m
16ft.
15m
49ft.
-
10m
33ft.
-
7.5m
25ft.
-
5m
16ft.
0.995
0m
0ft.
1.003
-5m
-16ft.
1.003
-7.5m
-25ft.
-
-10m
-33ft.
-
-15m
-49ft.
-
5m
16ft.
15m
49ft.
-
10m
33ft.
-
7.5m
25ft.
-
5m
16ft.
0.990
0m
0ft.
0.990
-5m
-16ft.
0.985
-7.5m
-25ft.
-
-10m
-33ft.
-
-15m
-49ft.
-
Height difference H
Outdoor unit
- (02 - 12) -
Pipe length
7.5m
10m
15m
25ft.
33ft.
49ft.
-
-
0.956
-
0.977
0.963
0.988
0.981
0.967
0.992
0.985
0.971
1.000
0.993
0.979
1.000
0.993
0.979
1.000
0.993
0.979
-
0.993
0.979
-
-
0.979
Pipe length
7.5m
10m
15m
25ft.
33ft.
49ft.
-
-
0.977
-
0.993
0.977
1.000
0.993
0.977
1.000
0.993
0.977
1.000
0.993
0.977
0.995
0.988
0.972
0.993
0.986
0.970
-
0.983
0.967
-
-
0.962
Outdoor unit
Indoor unit
Connection pipe
2 Indoor unit is under than outdoor unit.
20m
25m
66ft.
82ft.
0.942
0.928
0.950
0.936
0.953
0.940
0.957
0.943
0.965
0.951
0.965
0.951
0.965
0.951
0.965
0.951
0.965
0.951
20m
25m
66ft.
82ft.
0.958
0.939
0.958
0.939
0.958
0.939
0.958
0.939
0.958
0.939
0.953
0.934
0.951
0.932
0.948
0.930
0.944
0.925

Hide quick links: