CHAPTER 8 TAG ADDRESSES

Tag addresses are used to identify parameters in the controller and are identical to the Modbus addresses which are also listed
in the Series 2000 Communications Manual, Eurotherm Part No. HA 026230. Tag addresses are used with the demand data
protcol to set up input/output data in the PLC or supervisory PC.. They are repeated here in the order in which they appear in
the GSD file.
They can also be read from the Windows Configurator by pointing to the parameter and clicking the right mouse button.
Controller
Home Tab
Display
Parameter Description
Process Variable
Target setpoint
% Output power
For ON/OFF controllers the
following power levels must
be written:
Cool
-100%
OFF
0%
Heat
100%
Working set point. Read only:
use Target set point or
currently selected set point (1
to 16) to change the value
Auto-man select
0:
Auto
1:
Manual
Pot Position
Valve Posn (computed by
VP algorithm)
VP Manual Output (alterable
in Man only)
Heater current (With PDSIO
mode 2)
Customer defined
identification number
Setpoint Span
Error (PV-SP)
Remote Input Value

Status Tab

Summary Output Status Word
BIT
DESCRIPTION
0
Alarm 1 State
1
Alarm 2 State
2
Alarm 3 State
3
Alarm 4 State
4
Manual Mode
5
Sensor Break ( 0 = Good PV 1 = Sensor Broken )
6
Loop Break
7
Heater Fail
8
Tune Active
9
Ramp/Program Complete ( 0 = Running/Reset
10
PV out of range
11
DC control module fault (0= Good. 1= BAD)
2408 f and 2404 f PROFIBUS Communications Handbook
Tag
Address
1
2
3
5
273
317
53
60
80
629
552
39
26
Tag Address
75
( 0 = Safe 1 = Alarm )
( 0 = Safe 1 = Alarm )
( 0 = Safe 1 = Alarm )
( 0 = Safe 1 = Alarm )
( 0 = Auto 1 = Manual )
( 0 = Good closed loop
1 = Open Loop )
( 0 = No Fault
1 = Load fault detected )
( 0 = Auto Tune disabled
1 = Auto Tune active)
1 = Complete )
( 0 = PV within table range
1 = PV out of table range )
12
Programmer Segment Synchronise
13
Remote input sensor break ( 0 = Good, 1 = Bad)
14
IP1 Fault
15
Reserved
Status Tab
Fast Status Byte
BIT
DESCRIPTION
Bit 0
Alarm 1 State
( 0 = Safe 1 = Alarm )
Bit 1
Alarm 2 State
( 0 = Safe 1 = Alarm )
Bit 2
Alarm 3 State
( 0 = Safe 1 = Alarm )
Bit 3
Alarm 4 State
( 0 = Safe 1 = Alarm )
Bit 4
Manual Mode
( 0 = Auto 1 = Manual )
Bit 5
Sensor Break ( 0 = Good PV 1 = Sensor Broken )
Bit 6
Loop Break
( 0 = Good closed loop 1 = Open
Loop )
Bit 7
Heater Fail
( 0 = No Fault 1 = Load fault
detected )
Control Status Word
BIT
DESCRIPTION
0
Control algorithm Freeze
1
PV input sensor broken
2
PV out of sensor range
3
Self Tune failed
4
PID servo signal
5
PID debump signal
6
Fault detected in closed loop behaviour (loop
break)
7
Freezes the integral accumulator
8
Indicates that a tune has completed successfully
9
Direct/reverse acting control
10
Algorithm Initialisation flag
11
PID demand has been limited.
12
Autotune enabled
13
Adaptive tune enabled
14
Automatic Droop compensation enabled
15
Manual / Auto mode switch
Instrument Status Word
BIT
DESCRIPTION
0
Config/Oper mode switch
1
Disables limit checking
2
SRL ramp running (Read Only)
3
Remote setpoint active
4
Alarm acknowledge switch.
5
Reserved
6
Reserved
7
Reserved
8
Reserved
Tag Addresses
(0 = Waiting,
1 = Running)
Tag Address
74
76
77
8-1