Carrier 58DLA Installation, Start-Up, Operating And Service And Maintenance Instructions page 9

Table of Contents

Advertisement

CAUTION
!
FURNACE CORROSION HAZARD
Failure to follow this caution may result in furnace damage.
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements can corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol
sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products.
Location Relative to Cooling Equipment
The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers or
other flow control must prevent chilled air from entering the
furnace. If the dampers are manually operated, they must be
equipped with means to prevent operation of either unit unless
the damper is in the full- -heat or full- -cool position.
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
S
Section 9.3 of the NFGC NFPA 54/ANSI
Z223.1- -2009 , Air for Combustion and Ventilation,
and applicable provisions of the local building codes.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make- -up air MUST be provided for the ventilation devices,
in addition to that required by the furnace. Refer to Carbon
Monoxide Poisoning Hazard warning in venting section of
these instructions to determine if an adequate amount of
make- -up air is available.
The requirements for combustion and ventilation air depend upon
whether or not the furnace is located in a space having a volume
of at least 50 cubic feet per 1,000 Btuh input rating for all gas
appliances installed in the space.
S
Spaces having less than 50 cubic feet per 1,000 Btuh
require the OUTDOOR COMBUSTION AIR
METHOD.
S
Spaces having at least 50 cubic feet per 1,000 Btuh
may use the INDOOR COMBUSTION AIR,
STANDARD or KNOWN AIR INFILTRATION
METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper combus-
tion, ventilation, and dilution of flue gases using perman-
ent horizontal or vertical duct(s) or opening(s) directly
communicating with the outdoors or spaces that freely
communicate with the outdoors.
2. Fig. 7 illustrates how to provide TWO OUTDOOR
OPENINGS, one inlet and one outlet combustion and
ventilation air opening, to the outdoors.
e. One opening MUST commence within 12- -in. (300 mm)
of the ceiling and the second opening MUST commence
within 12- -in. (300 mm) of the floor.
f. Size openings and ducts per Fig. 7 and Table 2.
g. TWO HORIZONTAL DUCTS require 1- -in.
per 2,000 Btuh (1,100 mm
all gas appliances in the space per Fig. 7 and Table 2.
h. TWO OPENINGS OR VERTICAL DUCTS require
2
1- -in.
of free area per 4,000 Btuh (550 mm
combined input of all gas appliances in the space per Fig.
7 and Table 2.
3. ONE OUTDOOR OPENING requires:
2
a. 1- -in.
of free area per 3,000 Btuh (734 mm2/kW) for
combined input of all gas appliances in the space per
Table 2 and
b. Not less than the sum of the areas of all vent connectors
in the space.
The opening shall commence within 12- -in. (300 mm) of the
ceiling. Appliances in the space shall have clearances of at least
1- -in. (25 mm) from the sides and back and 6- -in. (150 mm) from
the front. The opening shall directly communicate with the
outdoors or shall communicate through a vertical or horizontal
duct to the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.
DUCTS
TO
O UTDOORS
12 " MAX
(305mm)
1 SQ IN.
PER 2000
B
BTUH*
DUCT S
TO
OUTDOORS
1 SQ IN.
PER 2000
A
BTUH*
12 " MAX
(305mm)
CIRCULA TING AIR DUCT S
*Minimum dimensions of 3 ---in. (76 mm.)
Use any of the following combinations of openings:
A & B C & D D & E F & G
Fig. 7 - - Air for Combustion, Ventilation, and Dilution for
Outdoors
Indoor Combustion Air - - NFPA & AGA
Standard and Known- -Air- -Infiltration Rate Methods
9
2
of free area
2
/kW) of combined input for
2
/kW) for
1 SQ IN.
PER 4000
BTUH*
12 "
D
(305mm)
MAX
VENT
THR OUGH
F
R OOF
1 SQ IN .
PER
4000
BTUH*
1 SQ IN .
PER
4000
BTUH*
E
G
12 "
(305mm)
MAX
C
12 " MAX
(305mm)
DUCT
1 SQ IN.
TO
PER 4000
OUTDOORS
BTUH*
A03174

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

58dlx

Table of Contents