Table of Contents

Advertisement

Fig. 53 - - Cleaning Heat Exchanger Cell
14. Reinstall internal vent pipe, if applicable.
15. Reinstall vent connector on furnace vent elbow. Securely
fasten vent connector to vent elbow with 2 field- -supplied,
corrosion- -resistant, sheet metal screws located 180_ apart.
16. Replace blower access door only, if it was removed.
17. Set thermostat above room temperature and check furnace
for proper operation.
18. Verify blower airflow and speed changes between heating
and cooling.
19. Check for gas leaks.
20. Replace outer access door.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury,
death and/or property damage.
Never test for gas leaks with an open flame.
commercially available soap solution made specifically for
the detection of leaks to check all connections.

Sequence of Operation

NOTE: Furnace control must be grounded for proper operation
or control will lock out. Control is grounded through
green/yellow wire routed to gas valve and manifold bracket
screw. Using the schematic diagram in Fig. 51, follow the
sequence of operation through the different modes. Read and
follow the wiring diagram very carefully.
NOTE: If a power interruption occurs during a call for heat (W),
the control will start a 90- -second blower- -only ON period two
seconds after power is restored, if the thermostat is still calling for
gas heating. The Amber LED light will flash code 12 during the
90- -second period, after which the LED will be ON continuous,
as long as no faults are detected. After the 90- -second period, the
furnace will respond to the thermostat normally.
The blower door must be installed for power to be conducted
through the blower door interlock switch ILK to the furnace
control CPU, transformer TRAN, inducer motor IDM, blower
motor BLWM, hot- -surface igniter HSI, and gas valve GV.
1. Heating
(See Fig. 25 for thermostat connections.)
The wall thermostat "calls for heat," closing the R- -to- -W
circuit. The furnace control performs a self- -check, verifies
the pressure switch contacts PRS are open, and starts the
inducer motor IDM.
a. Inducer Prepurge Period- - As the inducer motor IDM
comes up to speed, the pressure switch contacts PRS close
to begin a 15- -second prepurge period.
b. Igniter Warm- -Up- - At the end of the prepurge period,
the Hot- -Surface igniter HSI is energized for a 17- -second
igniter warm- -up period.
c. Trial- -for- -Ignition Sequence- - When the igniter warm- -
up period is completed, the main gas valve relay contacts
GVR close to energize the gas valve GV, the gas valve
opens, and 24 vac power is supplied for a field- -installed
humidifier at the HUM terminal. The gas valve GV per-
mits gas flow to the burners where it is ignited by the HSI.
Five seconds after the GVR closes, a 2- -second flame
proving period begins. The HSI igniter will remain ener-
gized until the flame is sensed or until the 2- -second flame
proving period begins.
d. Flame- -Proving- - When the burner flame is proved at the
flame- -proving sensor electrode FSE, the furnace control
CPU begins the blower- -ON delay period and continues
A91252
to hold the gas valve GV open. If the burner flame is not
proved within two seconds, the control CPU will close
the gas valve GV, and the control CPU will repeat the ig-
nition sequence for up to three more Trials- -For- -Ignition
before going to Ignition- -Lockout. Lockout will be reset
automatically after three hours or by momentarily inter-
rupting 115 vac power to the furnace, or by interrupting
24 vac power at SEC1 or SEC2 to the furnace control
CPU (not at W, G, R, etc.).
If flame is proved when flame should not be present, the
furnace control CPU will lock out of Gas- -Heating mode
and operate the inducer motor IDM until flame is no
longer proved.
e. Blower- -On Delay- - If the burner flame is proven, the
blower motor is energized on HEAT speed 25 seconds
after the gas valve GV is energized.
Simultaneously, the electronic air cleaner terminal
EAC- -1 is energized and remains energized as long as the
blower motor BLWM is energized.
f. Blower- -Off Delay- - When the thermostat is satisfied, the
R- -to- -W circuit is opened, de- -energizing the gas valve
Use a
GV, stopping gas flow to the burners, and de- -energizing
the humidifier terminal HUM. The inducer motor IDM
will remain energized for a 5- -second post- -purge period.
The blower motor BLWM and air cleaner terminal
EAC- -1 will remain energized for 90, 120, 150, or 180
seconds (depending on the blower- -OFF delay selection).
The furnace control CPU is factory- -set for a 120- -second
blower- -OFF delay.
2. Cooling Mode
The thermostat "calls for cooling."
a. Single- -Speed Cooling
(See Fig. 25 - - 32 for thermostat connections)
The thermostat closes the R- -to- -G- -and- -Y circuits. The
R- -to- - Y circuit starts the outdoor unit, and the R- -to- -
G- -and- -Y/Y2 circuits start the furnace blower motor
BLWM on COOL speed.
The electronic air cleaner terminal EAC- -1 is energized
with 115 vac when the blower motor BLWM is operating.
When the thermostat is satisfied, the R- -to- -G- -and- -Y cir-
cuits are opened. The outdoor unit will stop, and the fur-
nace blower motor BLWM will continue operating on the
COOL speed for an additional 90 seconds. Jumper Y/Y2
to DHUM to reduce the cooling off- -delay to 5 seconds.
(See Fig. 24.)
b. Two- -Speed Cooling
(See Fig. 25- -32 for thermostat connections.)
The thermostat closes the R- -to- -G- -and- -Y1 circuits for
low- -cooling or closes the R- -to- -G- -and- -Y1- -and- -Y2 cir-
cuits for high- -cooling. The R- -to- -Y1 circuit starts the
outdoor unit on low- -cooling speed, and the R- -to- -
G- -and- -Y1 circuit starts the furnace blower motor
BLWM on low- -cool speed (same speed as FAN). The
R- -to- -Y1- -and- -Y2 circuits start the outdoor unit on high- -
cooling speed, and the R- -to- -G and- - Y/Y2 circuits start
49

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

58dlx

Table of Contents