8-6. Overload Protection

3
Located behind front panel.
1
Y Stop engine.
Tools Needed:
.
3/8 in
1
CB5 protects the 24 volt ac output to
Remote receptacle RC4. If CB5
opens, 24 volt ac output to RC4 stops.
2
2
3
Remove cover.
Fuse F1 is located on power board
PC7. F1 protects the exciter stator
from overload. If F1 opens, weld and
generator power output stops.
Fuse F2 is located behind front panel.
F2 protects the 115 volt ac output to
Remote receptacle RC4. If F2 opens,
115 volt ac output to RC4 stops.
Replace fuse(s) if open. Reinstall
cover before operating unit.
4
F6 protects the engine wiring system
from overload. If F6 opens, the engine
will not crank. Replace fuse if open.
When a circuit breaker or fuse
opens, it usually indicates a more
serious problem exists. Contact
a Factory Authorized Service
Agent.
Circuit Breaker CB5
Fuse F1 (See Parts List)
Fuse F2 (See Parts List)
Fuse F6 (See Parts List)
4
802 851-A / Ref. 211 909
OM-4411 Page 33