WARNING: Only qualified personnel should service internal components or electrical
wiring.

LOCATION

Locate the icemaker dispenser indoors in a well ventilated area. Avoid exposure to direct sunlight and/or heat
caused by radiation. Ambient room temperature must be in the range of 60° to 90° F. Do not install unit in an
enclosed area where heat build-up could be a problem. Note: Air flow direction and spacing required shown in
Figure 1.
Consult Figure 1 for utility connection locations.

PLUMBING

Connect the icemaker to a cold, potable water source, suitable for drinking. This water source must comply with
the basic plumbing code of the Building Officials and Code Administrators International Inc. (BOCA) and the
Food Service Sanitation Manual of the Food and Drug Administration. Do not install unit on a water softener
line. It is recommended that a hand shut-off valve and strainer be used on the incoming supply line. (See Figure
1 for size and location.) For proper operation of the incoming water supply pressure must be in the range of
30-90 PSIG. Install a pressure regulating valve if above this range!
IMPORTANT: To insure proper icemaker operation and also to reduce the frequency of water-related
service problems, a water filter should be installed. REMCOR recommends the use of IMI Cornelius
filter, model number 81COR01PS.
For specific recommendations on these filter systems for your local water conditions, consult with a distributor in
your area or contact the filter manufacturer.
Connect separate drain lines to all drain connections. See Figure 2 for size and location. These lines must pitch
downward to and open drain and must contain no traps, or improper drainage will result. All drain connections
must be in accordance with the basic plumbing code of the Building Officials and Code Administrators Interna-
tional (BOCA) and local codes.
NOTE:
In areas where consistently warm water temperatures are encountered, the use of a pre-cooler
in the water line is recommended to maximize the ice production of this unit.

MODEL LP650R ONLY: REMOTE CONDENSER INSTALLATION

Remcor Products remote condenser systems come in three separate packages to complete one remote con-
denser application. They consist of the icemaker, the remote condenser and the interconnecting pre-charged
line set.

Icemaker

The refrigeration system of a remote condenser systems is similar to a standard air cooled system with the fol-
lowing exceptions described below:
Mixing Valve
This valve is located at the condenser and serves as a head pressure regulating valve. As the temperature at
the condenser drops, the head pressure at the receiver will drop. When this pressure reaches 225 PSIG, the
mixing valve by-passes the condenser and meters hot discharge gas into the receiver, maintaining the 225
PSIG receiver pressure.

INSTALLATION

3
91424