9 Settings
118
Note
The burner hours are only counted, when the maintenance mes­
sage has been activated.
Burner start interval (7042)
Setting of the interval for burner starts for maintenance.
Burn starts since maint (7043)
Burner starts since the last maintenance.
Note
The burner starts are only counted, when the maintenance mes­
sage has been activated.
Maintenance interval (7044)
Setting of maintenance interval in months.
Time since maintenance (7045)
Passed time since the last maintenance interval.
Note
The time is only counted, when the maintenance message has
been activated.
Fan speed ionization current (7050)
Speed limit from which the ionisation current service alarm should be set
(prog. no. 7051), if the ionisation current monitoring and therefore a speed
increase based on too low ionisation current active is.
Message ionization current (7051)
Function for display and reset of the burner ionization current maintenance
message. The maintenance message can only be reset if the reason for
maintenance has been eliminated.
Chimney sweep function (7130)
The chimney sweep function is switched on or off under this prog no.
Note
The function is switched off by the settingOff or automatically if the
maximum boiler temperature is reached.
It can also be directly activated via the chimney sweep button.
Manual control (7140)
Activation of manual control. If the manual control function is activated the
boiler is controlled to the setpoint manual control. All the pumps are
switched on. Additional request will be ignored!
Controller stop function (7143)
If the controller stop function is activated, the burner output set in the set­
point controller stop is directly requested by the device.
Controller stop setpoint (7145)
With activated controller stop function the output set here is requested by
the device.
Telephone customer service (7170)
Here the desired telephone number of customer service can be entered.
PStick storage pos (7250)
The parameterPStick storage pos can be used to select the data set (data
set number on the stick) to be written or read.
PStick command (7252)
No operation: This is the basic state. As long as no operation is active
on the stick, this command is displayed.
7636047 - 02 - 24082015