9 Settings
Tab.11 Check no. heat source 1 (prog.-no. 6212)
A collector field
Tank charging
with sensor B6
pump for
and collector pump
buffer storage tank
Q5
K8
0
1
3
5
6
8
9
10
11
12
13
14
15
114
40 for buildings with thick walls or outer insulation.
20 for buildings of normal building design.
10 for buildings of light building design.
The central setpoint lead monitors the heat generator setpoint to the re­
quired central flow temperature. With the setting the maximum corrector is
restricted, even if a larger adaptation should be required.
The heating circuit pump is activated without heat request subject to out­
side temperature. If the outside temperature reaches the lower limit value
of -4°C, the heating circuit pump is activated. The pump is activated every
6 hours for 10 minutes when the outside temperature is between -5°C and
+1.5°C. When the upper limit value of 1.5°C is reached, the pump
switches off.
Sensor modes can be saved under prog. no. 6200. This is done automati­
cally; however, after change of the heating system (removal of a sensor)
the state must be saved again to the sensor terminals.
The factory setting of the regulator is written to the regulator.
(6213), Check no. storage tank (6215) and (6217)Check no.
heating circuits
The standard device generates a check number to identify the system
scheme; this comprises the numbers listed in the table below.
Solar diverting
valve for
buffer storage tank
K8
X
X
X
X
X
X
X
X
Central setp compensation (6117)
System frost protection (6120)
Save sensors (6200)
Reset to default parameters (6205)
Caution
The regulator parameters are overwritten. The factory settings are
stored in the regulator.
Activation of prog. no. 6205:
The regulator is reset to factory setting.
Check no. heat source 1 (6212), Check no. heat source 2
Solar
Solar charging
pump for
swimming pool K18
No solar
X
External solar ex­
changer, Solar
Solar diverting
pump K9
valve for
DHW=DHW stor­
swimming pool K18
age tank
B=Buffer storage
tank
X
7636047 - 02 - 24082015
*
DHW/B
DHW+B
DHW/B
DHW
DHW
P
P