Napoleon LHD45P Installation And Operating Instructions Manual page 29

Table of Contents

Advertisement

Available languages

Available languages

FRAMING
ROUGH OPENING
HEIGHT
WIDTH
DEPTH
41 ¼"
46 ¾"
20 ¹/
(1048mm)
(1188mm)
(511mm)*
* When constructing the enclosure allow for fi nishing material thickness to maintain clearances.
** HORIZONTAL VENT SECTIONS: A minimum clearance of 2" (51mm) to the top and 1" (25mm) to the
sides and bottom of the vent pipe on all horizontal runs to combustibles is required. Horizontal vent sections
within enclosures require a minimum clearance of 6" (152mm) at the top of the vent pipe, see "MINIMUM
CLEARANCE TO COMBUSTIBLE ENCLOSURES" section. Use fi restop spacer W010-1777 (supplied).
** VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs
to combustibles is required except for clearances in appliance enclosures. Vertical vent sections within
enclosures require a minimum clearance of 2" (51mm) around the vent pipe. Use fi restop spacer W500-0096
(not supplied).
OUTSIDE
CHASE
46 3/4" 1187mm
20 1/8"
511mm
46 3/4" 1187mm
MAINTAIN THESE MINIMUM CLEARANCES TO COMBUSTIBLES FROM
APPLIANCE AND VENT SURFACES:
TO
TO CEILING
CEILING
FROM TOP
FROM
OF
BASE OF
APPLIANCE
APPLIANCE
OPENING
"
56"
30 ¹¹/
"
8
16
(1422mm)
(780mm)
20 1/8"
511mm
INSIDE
CHASE
2" 51mm
SIDE
TO
TOP OF
WALL
COMBUSTIBLE
FINISHING
ABOVE
APPLIANCE
2"
14"
(51mm)
(356mm)
(51mm)**
52"
1320mm
46 3/4" 1187mm
BACK WALL OF CHASE / ENCLOSURE
(INCLUDING ANY FINISHING MATERIAL)
73 1/2"
1867mm
29
SIDES
REAR
VENT
AND
& SIDE
PIPE
BOTTOM
STAND-
OF VENT
OFFS
PIPE
2"
1"
0"
(25mm)**
(0mm)
MIN
W415-1335 / 06.27.14
EN