Installation - Desa VFF-32S-AKA Owner's Operation And Installation Manual

Unvented (vent-free) universal firebox
Hide thumbs Also See for VFF-32S-AKA:
Table of Contents

Advertisement

AIR FOR COMBUSTION
AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un-
confined space. When ventilating to an adjoining
unconfined space, you must provide two perma-
nent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting
the two spaces (see options 1 and 2, Figure 4). You
can also remove door into adjoining room (see
option 3, Figure 3). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation for required size of
ventilation grills or ducts.
Ventilation
Grills
Into Adjoining
Or
Room,
Remove
Option 1
Door into
Adjoining
Room,
Option
3
12"
Figure 3 - Ventilation Air from Inside
Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
one within 12" of the ceiling and one within 12"
of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These
spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet
or outlet air into attic if attic has a thermostat-
controlled power vent. Heated air entering the attic
will activate the power vent.
116208-01C
12"
Ventilation Grills
Into Adjoining Room,
Option 2
www.desatech.com
Outlet
Air
Outlet
Air
Inlet
Air
Inlet Air
Figure 4 - Ventilation Air from Outdoors

INSTALLATION

WARNING: A qualified ser-
vice person must install firebox.
Follow all local codes.
WARNING: Never install the
firebox
• in a bedroom or bathroom*
• in a recreational vehicle
• where curtains, furniture,
clothing or other flammable
objects are less than 42" from
the front, top or sides of the
firebox
• in high traffic areas
• in windy or drafty areas
* Unless the installed log set is
rated at 10,000 Btu/Hr or less.
CAUTION: Log heaters
installed in this firebox create
warm air currents. These cur-
rents move heat to wall surfaces
next to firebox. Installing firebox
next to vinyl or cloth wall cover-
ings or operating firebox where
impurities (such as, but not
limited to, tobacco smoke, aro-
matic candles, cleaning fluids,
oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
Ventilated
Attic
To Attic
To
Crawl
Space
Ventilated
Crawl Space