S-16E Blower Performance Data - Goodman ASX Service Instructions Manual

Hide thumbs Also See for ASX:
Table of Contents

Advertisement

SERVICING
THERMOSTAT "FAN ONLY" MODE
During Fan Only Operations, the CFM output is 30% of the
cooling setting.
CFM TRIM ADJUST
Minor adjustments can be made through the dip switch
combination of 7-8. Table 4 shows the switch position for this
feature.
NOTE: The airflow will not make the decreasing adjustment
in Electric Heat mode.
C FM
S w itc h 7
+ 1 0 %
-1 5 %
Table 4
HUMIDITY CONTROL
When using a Humidstat (normally closed), cut jumper PJ6
on the control board. The Humidstat will only affect cooling
airflow by adjusting the Airflow to 85%.
TWO STAGE HEATING
When using staged electric heat, cut jumper PJ4 on the
control board.

S-16E BLOWER PERFORMANCE DATA

SPEED
HIGH
MEDIUM
LOW
NOTE: External static is for blower @ 230 Volts. It does not include Coil, Air Filter or Electric Heaters.
S w itc h 8
O N
O F F
O F F
O N
MBR800**-*
STATIC
SCFM
0.1
1,240
0.2
1,170
0.3
1,120
0.4
1,060
0.5
980
0.6
900
0.1
900
0.2
850
0.3
790
0.4
740
0.5
680
0.6
605
0.1
650
0.2
590
0.3
540
0.4
500
0.5
430
0.6
330
AEPF DIPSWITCH FUNCTIONS
Model
Switch 1
OFF
AEPF1830
OFF
OFF
AEPF3036/4260
OFF
Model
Switch 5
OFF
AEPF1830
OFF
OFF
AEPF3036/4260
OFF
1
7 - 8 shall be OFF-ON for 2.5 ton applications
MBR1200**-*
MBR1600**-*
SCFM
SCFM
1,500
1,800
1,460
1,740
1,360
1,680
1,280
1,610
1,200
1,520
1,110
1,430
1,380
1,540
1,320
1,490
1,270
1,450
1,200
1,400
1,140
13,560
1,040
1,280
1,170
1,130
1,130
1,100
1,080
1,070
1,020
1,030
950
990
830
930
EMERGENCY
Switch 2
BACKUP CFM
1
1100
OFF
OFF
850
ON
ON
700
OFF
2050
OFF
1750
ON
ON
1600
ON
ON
1200
ON
ON
1020
Table 5
EMERGENCY
Switch 6
BACKUP CFM
OFF
1100
OFF
850
ON
ON
700
OFF
1800
OFF
1580
ON
ON
1480
ON
ON
1200
ON
ON
1020
Table 6
MBR2000**-*
SCFM
2,160
2,080
1,990
1,890
1,790
1,690
1,730
1,670
1,590
1,520
1,420
1,320
1,520
1,450
1,360
1,290
1,200
1,090
HEAT PUMP CFM
WITH BACKUP
1210
935
770
2150
1835
1680
1260
1020
HEAT PUMP CFM
WITH BACKUP
1100
850
600
1800
1580
1480
1200
1020
37