Installation; General Information; Heating System Connection; Electrical Connection - Dimplex LA 9MS Installation And Operating Instructions Manual

Air-to-water heat pump for outdoor installation
Table of Contents

Advertisement

6
6

Installation

6.1 General Information

The following connections need to be established on the heat
pump:
Flow and return flow of the heating system
Condensate outflow
Control line to the heat pump manager
Power supply

6.2 Heating System Connection

The heating system connections on the heat pump have a 1" ex-
ternal thread. Route the connection hoses out of the device in a
downwards direction. Use a spanner to firmly grip the transitions
when connecting the heat pump.
Before connecting the heating water system to the heat pump,
the heating system must be flushed to remove any impurities,
residue from sealants, etc. Any accumulation of deposits in the
liquifier could cause the heat pump to completely break down.
For systems in which the heating water flow can be shut off via
the radiator or thermostat valves, an overflow valve must be in-
stalled in a heating bypass behind the heat pump by the cus-
tomer. This ensures a minimum heating water flow rate through
the heat pump and helps to avoid faults.
Once the heating system has been installed, it must be filled, de-
aerated and pressure-tested.
Consideration must be given to the following when filling the sys-
tem:
Untreated filling water and make-up water must be of drink-
ing water quality
(colourless, clear, free from sediments)
Filling water and make-up water must be pre-filtered (pore
size max. 5µm).
Scale formation in hot water heating systems cannot be com-
pletely avoided, but in systems with flow temperatures below
60°C the problem can be disregarded.
With medium and high-temperature heat pumps, temperatures
above 60°C can be reached.
The following standard values should therefore be adhered to
concerning the filling water and make-up water (according to VDI
2035 Sheet 1):
Total alkaline earths
Total heat
in mol/m³ and/or
output in [kW]
up to 200
200 to 600
> 600
Minimum heating water flow rate
The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating sys-
tem.This can be accomplished, for example, by installing either a
dual manifold without differential pressure or an overflow
valve.The procedure for adjusting an overflow valve is described
in the Chapter Start-Up. When the minimum flow rate is under-
shot drastically, the plate steel exchanger in the refrigerating
cycle can freeze, which can lead to total loss of the heat pump.
5
Total
hardness in dH
mmol/l


2.0
11.2


1.5
8.4
< 0.02
< 0.11
NOTE
The use of an overflow valve is only recommended for panel heating and
a max. heating water flow of 1.3 m³/h.
System faults may result if this is not observed.
Antifreeze
A method of manual drainage (see illustration) should be pro-
vided for heat pumps which are exposed to frost. The antifreeze
function of the heat pump manager is active whenever the heat
pump manager and the heat circulating pump are ready for oper-
ation. If the heat pump is taken out of service or in the event of a
power failure, the system has to be drained. The heating circuit
should be operated with a suitable antifreeze if heat pump sys-
tems are implemented in buildings where a power failure can not
be detected (holiday home).

6.3 Electrical Connection

The power connection of the heat pump is effected via a stan-
dard 3-core cable.
The cable has to be supplied by the client and the wire cross-sec-
tion to be selected according to the power consumption of the
heat pump (see Equipment Data in the appendix) as well as the
relevant EN (VDE) and VNB regulations.
The power supply of the heat pump must be equipped with a dis-
connecting device with a contact gap of at least 3 mm (e.g. utility
service contactor, power contactor) as well as a 1-pole automatic
circuit breaker (tripping current as stated in the Equipment Data).
The control voltage is supplied via the heat pump manager.
The heat pump manager has a 230 V AC-50 Hz power supply.
Connect the manager in compliance with its own operating in-
structions (see type plate for fuse protection).
The control line (not included in scope of supply) is connected to
the heat pump manager using the two rectangular plug connec-
tors. The plug connector on the switch box must be used close to
the pivotal point in the heat pump. More detailed information can
be found in the operating instructions of the heat pump manager.
For detailed information, see Circuit Diagrams in the Appendix.

Advertisement

Table of Contents
loading

Table of Contents