Tripp Lite SmartOnline Series Owner's Manual
Tripp Lite SmartOnline Series Owner's Manual

Tripp Lite SmartOnline Series Owner's Manual

Rack/tower on-line ups systems
Hide thumbs Also See for SmartOnline Series:

Advertisement

Quick Links

1. Important Safety Instructions
2. Installation
2.1 Mounting (Rack)
2.2 Mounting (Tower)
2.3 Connection and Start-Up
2.4 Optional Connections
3. Operation
3.1 Front Panel Switches
3.2 Advanced Operational Settings
3.3 Front Panel Indicator Lights
3.4 Rear Panel
3.5 Communications
4. Troubleshooting
5. Battery Replacement
6. Storage and Service
6.1 Storage
6.2 Service
7. Warranty Registration
Español
Français
Copyright © 2008 Tripp Lite. All rights reserved. SmartOnline
Owner's Manual
SmartOnline
Rack/Tower On-Line UPS Systems
Not suitable for mobile applications.
1111 W. 35th Street, Chicago, IL 60609 USA
Customer Support: (773) 869-1234 • www.tripplite.com
is a trademark of Tripp Lite.
2
3
3
4
4
5
7
7
7
8
10
11
12
13
15
15
15
15
16
31

Advertisement

Table of Contents
loading

Summary of Contents for Tripp Lite SmartOnline Series

  • Page 1 6. Storage and Service 6.1 Storage 6.2 Service 7. Warranty Registration Español Français 1111 W. 35th Street, Chicago, IL 60609 USA Customer Support: (773) 869-1234 • www.tripplite.com Copyright © 2008 Tripp Lite. All rights reserved. SmartOnline is a trademark of Tripp Lite. ™...
  • Page 2: Important Safety Instructions

    UPS system. • Do not use extension cords to connect the UPS system to an AC outlet. Using anything other than Tripp Lite surge suppressors to connect the UPS system to an outlet will void the warranty. • If the UPS system receives power from a motor-powered AC generator, the generator must provide clean, filtered, computer-grade output.
  • Page 3: Installation

    Use the included rackmount shelves and mounting hardware to mount the UPS system in a 4-post rack or rack enclosure. To mount the UPS system in a 2-post (telecom) rack, order Tripp Lite’s 2-Post Rackmount Kit (model 2POSTRMKITWM, sold separately). •...
  • Page 4: Mounting (Tower)

    ( continued ) 2.2 Mounting (Tower) The UPS system can be mounted in an upright tower position when used with Tripp Lite’s optional base stand kit (model 2-9USTAND, sold separately). When mounting the UPS system in a tower position, make sure the control panel is closer to the top of the cabinet than the bottom.
  • Page 5: Optional Connections

    2. Installation ( continued ) 2.3 Connection and Start-Up ( continued ) Plug equipment into the UPS system’s AC outlets. The UPS system is designed to support computer equipment only. The UPS system will become overloaded if household appliances or laser printers are connected to its outlets.
  • Page 6: External Battery Connection

    2. Installation ( continued ) 2.4 Optional Connections ( continued ) EPO Port Connection This optional feature is only for applications that require connection to a facility’s Emergency Power Off (EPO) circuit. Connecting the EPO circuit to the UPS system’s EPO port enables emergency shutdown of the UPS system.
  • Page 7: Operation

    3. Operation 3.1 Front Panel Switches “ON/TEST” Button: This button controls 4 separate functions: UPS System Power ON To turn on the UPS system, press the “ON/TEST” button for approximately 1 second until the UPS system beeps, then release the button.
  • Page 8: Advanced Operational Settings

    3. Operation ( continued ) 3.2 Advanced Operational Settings ( continued ) Economy mode can be enabled (or disabled) through the included PowerAlert software or the optional SNMPWEBCARD internal accessory card. The UPS system's yellow “BYPASS” LED will illuminate continuously when economy mode is enabled. Refer to the PowerAlert or SNMPWEBCARD documentation for more information.
  • Page 9 AC line power, but will not receive battery power during a blackout. In this case, contact Tripp Lite for service. “FAULT” LED: This red LED will flash when the UPS system detects an internal fault.
  • Page 10: Rear Panel

    3. Operation ( continued ) 3.4 Rear Panel Accessory Card Slot: Remove the cover panel from this slot to install an optional internal SNMPWEBCARD or RELAYIOCARD accessory, sold separately. SNMPWEBCARD provides a network interface for monitoring and control via SNMP, Web or telnet, enabling remote reboots, shutdowns and more.
  • Page 11 3.5 Communications Communication Ports (USB and/or RS-232): These ports connect the UPS system to a computer. Use with Tripp Lite’s PowerAlert software and included cabling to allow the computer to automatically save open files and shut down during a blackout. Also...
  • Page 12: Troubleshooting

    BATT 25% Initialization: Shut down the UPS system. Check the internal battery connections. Correct the AC input voltage. Restart the UPS system. If the problem persists, contact Tripp Lite for service. FAULT Utility Voltage Low and Battery Disconnected in On-Line...
  • Page 13: Battery Replacement

    Batteries are recyclable. Refer to local codes for disposal requirements or in the USA only call 800-SAV-LEAD or 800-8-BATTERY (800-822-8837) or visit www.rbrc.com for recycling information. • Tripp Lite offers a complete line of UPS system Replacement Battery Cartridges (R.B.C.). Go to www.tripplite.com/support/battery/ to locate the specific replacement battery for the UPS system.
  • Page 14 5. Battery Replacement ( continued ) Procedure Remove Front Panel Remove Battery Compartment Cover Disconnect Old Batteries and Remove Old Batteries Insert New Batteries and Connect New Batteries (Attach battery connectors black-to-black and red-to-red.) Replace Battery Compartment Cover Replace Front Panel Recycle Old Batteries...
  • Page 15: Storage And Service

    Regulatory Compliance Identification Numbers: For the purpose of regulatory compliance certifications and identification, this Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number.
  • Page 16 1111 W. 35th Street, Chicago, IL 60609 USA 773.869.1234 (USA) • 773.869.1212 (International) www.tripplite.com 2009XXXXX 93-2835_EN...

Table of Contents