en | System Configuration
Notification appliance 1 zone assignment
5
1
1
1
ACK
Notification appliance 2 zone assignment
See "Notification appliance 1 zone assignment", Notification
appliance 1 zone assignment, page 50.
Reactivating notification appliances
5
1
3
1
2014.06 | 7.0 | F.01U.172.980
Press zone key 5.
This takes you to the Output Config menu.
Press zone key 1.
This takes you to the NAC submenu.
Press zone key 1.
This takes you to the NAC Zones submenu.
Use the zone keys to select the corresponding zones
8
whose alarm you want to activate notification
...
appliance 1.
You can select multiple zones. If you press the zone
key again, the selection is cancelled.
Confirm your selection.
Press zone key 5.
This takes you to the Output Config menu.
Press zone key 1.
This takes you to the NAC submenu.
Press zone key 3.
This takes you to the Reactive NAC submenu.
Press zone keys 1 or 2.
2
1=By Other Zone (default setting)
...
2 No Reactivate
Conventional Fire Panel