Relay Outputs - Bosch FPC-500-2 Installation Manual

Conventional fire panel
Hide thumbs Also See for FPC-500-2:
Table of Contents

Advertisement

Conventional Fire Panel
Notice!
Connect the notification appliances to the terminals NAC1
and/or NAC2. This connection is EN 54‑13 (BOSEC certificate
TCC 2 - 977) compliant.
3.3.5

Relay Outputs

Notice!
The fault relay is activated in a normal state. It is opened in the
event of a fault.
The fire panel has two relay outputs. The relays work as
potential-free change-over contacts.
The alarm relay is activated by every fire alarm.
Notice!
A transmission device must be installed in the immediate
vicinity (without a space) of the FPC‑500‑x.
The connecting line between the fire panel and the
transmission device must not be exposed, as it is not
monitored.
Notice!
Both relay outputs "ALARM" and "FAULT" can switch a
maximum of 1 A @ 30 VDC each.
Bosch Sicherheitssysteme GmbH
NO C NC
NO C NC
ALARM
FAULT
Installation | en
2014.06 | 7.0 | F.01U.172.980
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fpc-500-4Fpc-500-8

Table of Contents