g
Digital Energy
SG Series Uninterruptable Power Supply
225-300kVA UL listed with eBoost
Topology
Nominal output power at pf = 0.9 lag.
System Efficiency in Double Conversion operating mode
@0.9 pf lagging load, nominal voltage/frequency, energy storage disconnected
System Efficiency in eBoost Operating mode
@0.9 pf lagging load, nominal voltage/frequency, energy storage disconnected
Heat rejection in Double Conversion operating mode
@0.9 pf lagging load, nominal voltage/frequency, energy storage disconnected
Heat rejection in eBoost Operating mode
@0.9 pf lagging load, nominal voltage/frequency, energy storage disconnected
Max Cooling Air (77°F - 86°F / 25°C - 30°C) (225/300kVA)
Audible noise level (at 5 ft./1.52Mts)
Operating temperature range
Storage temperature range
Relative humidity
Maximum Altitude
g
imagination at work
Energy
Digital Energy
Technical Data Sheet - 225-300kVA UL Listed
225kVA with 5th filter
300kVA with 5th filter
225kVA with 5th filter
300kVA with 5th filter
Double Conversion Mode
eBoost Mode
TM
General Data
25% load
85.5%
225kVA with 5th filter
89.0%
300kVA with 5th filter
25% load
225kVA with 5th filter
95.5%
300kVA with 5th filter
96.6%
25% load
50% load
29295
31270
8.6
9.2
28466
37888
8.3
11.1
25% load
50% load
8140
8495
2.4
2.5
8106
8922
2.4
2.6
UPS
32°F - 104°F (0°C - 40°C)
Battery
68°F - 77°F (20°C - 25°C)
(Note: Higher temperatures shorten battery life)
UPS
5°F - 122°F (-15°C to +50°C)
Battery
32°F - 104°F (0°C - 40°C)
(VRLA)
Storage time is 6 months at 77°F (25°C).
(Note: Higher temperatures reduce battery storage time)
0-95%, non-condensing
3281 / 1000 (no derating)
4921ft
6562ft
(1500Mts)
(2000Mts)
-5%
-9%
True On-line double conversion
300kVA (270kW) / 225kVA (202.5kW)
50% load
75% load
91.7%
92.8%
92.4%
92.8%
50% load
75% load
97.6%
98.3%
98.1%
98.5%
75% load
100% load
40207
52807
11.8
15.5
53609
73623
15.7
21.6
75% load
100% load
8962
10522
2.6
3.1
10522
12134
3.1
3.6
2661 / 3709 CFM
67 dB(A)
60 dB(A)
8202ft
9843ft
(2500Mts)
(2500Mts)
-14%
-18%
GEA-D2041 (225 300kVA TDS), Page: 1
100% load
92.9%
92.6%
100% load
98.5%
98.7%
BTU/hr
kW
BTU/hr
kW
BTU/hr
kW
BTU/hr
kW
ft (M)
ft
(M)
Derating