Safety Notes - Bosch BCM-0000-B Installation Manual

Hide thumbs Also See for BCM-0000-B:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 17
BCM-0000-B

Safety Notes

NOTICE!
-
-
-
i
-
-
-
-
Functions
The module monitors the power supply for the complete panel and regulates
battery charging as a function of time and temperature. The button has
three functions, which are dependent on the status of the battery controller
module:
-
The four module LEDs light up as a confirmation and LED test each time
the button is pressed.
-
If the batteries have a voltage of between 18 V and 21 V, the battery
loading procedure can be started manually. Please note that a power
supply must be available.
-
The 24 V switch outputs can be reset. The switch output is deactivated
if a fault occurs.
Bosch Sicherheitssysteme GmbH
Installation must only be carried out by authorized
personnel.
The BCM-0000-B can only be used with panel controllers
FPA-1200-MPC and MPC-xx00-B with software versions
from 2.1 onwards.
The total current for all connected components, including
the battery charge current, must not exceed 6 A.
The 24 V switch outputs must not be connected in parallel.
The batteries connected to BCM-0000-B must all be the
same type and have the same electrical features.
The length of the cable on the fault switch outputs must
not exceed 3 meters (approx. 9.8 feet).
The cables on the fault switch outputs must only be
installed within the housing.
en
F.01U.081.382 | 3.0 | 2009.07
17

Advertisement

Table of Contents
loading

Table of Contents