GE AF-650 GP Programming Manual page 139

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
LC-10 Comparator Operand
Option:
3
3
[0]
DISABLED
*
[1]
Reference %
[2]
Feedback %
[3]
Motor speed
[4]
Motor Current
[5]
Motor torque
[6]
Motor power
[7]
Motor Rated
Voltage
[8]
DC-link voltage
[9]
Motor Thermal
[10]
Drive thermal
[11]
Heat sink temp.
[12]
Analog input
AI53
[13]
Analog input
AI54
[14]
Analog input
AIFB10
[15]
Analog input
AIS24V
[17]
Analog input
AICCT
[18]
Pulse input FI29 Value is in percent.
[19]
Pulse input FI33 Value is in percent.
[20]
Alarm number
[21]
Warning
number
[22]
Analog input
x30 11
[23]
Analog input
x30 12
[30]
Counter A
[31]
Counter B
[32]
Process PID
Error
138
Function:
Options [1] Reference % to [31] Counter B
are variables which are compared based
on their values. Options [50] FALSE to
[186] Drive in auto mode are digital
values (true/false) where the comparison
is based on the amount of time during
which they are set to true or false. See
parameter LC-11 Comparator Operator.
Select the variable to be monitored by
the comparator.
The comparator is disabled.
The resulting remote reference in
percent.
[RPM] or [Hz], as set in
parameter K-02 Motor Speed Unit.
[RPM] or [Hz], as set in
parameter K-02 Motor Speed Unit.
Value is in percent.
Value is in percent.
Value is in percent.
Value is in percent.
Value is in percent.
AIFB10 is internal 10 V supply.
AIS24V is a 24 V switch mode power
supply.
Value is in [°]. AICCT is control card
temperature.
The number or registered alarms.
Value of the PID error
(parameter PI-60 Process PID Error).
02/2016 All rights reserved.
LC-10 Comparator Operand
Option:
Function:
[33]
Process PID
Value of the PID output
Output
(parameter PI-61 Process PID Output).
[43]
Analog input
X49/1
[44]
Analog input
X49/3
[45]
Analog input
X49/5
[50]
FALSE
Use to enter the fixed value of false in
the comparator.
[51]
TRUE
Use to enter the fixed value of true in
the comparator.
[52]
Control ready
Use to enter the control board receives
supply voltage.
[53]
Drive ready
The frequency converter is ready for
operation and applies a signal on the
control board.
[54]
Running
The motor runs.
[55]
Reversing
The output is active when the frequency
converter runs counterclockwise (the
logical product of the status bits running
AND reverse).
[56]
In range
The motor runs within the programmed
current and speed ranges set in
parameter H-70 Warning Current Low to
parameter H-73 Warning Speed High.
[60]
On reference
The motor runs on reference.
[61]
Below
The motor runs at a reference which is
reference, low
less than the value in
parameter H-74 Warning Reference Low.
[62]
Above ref, high
The motor runs at a reference which
exceeds the value in
parameter H-75 Warning Reference High.
[65]
Torque limit
The torque exceeds the value in
parameter F-40 Torque Limiter (Driving) or
parameter F-41 Torque Limiter (Braking).
[66]
Current Limit
The motor current exceeds the value in
parameter F-43 Current Limit.
[67]
Out of current
The motor current is outside the range
range
set in parameter F-43 Current Limit.
[68]
Below I low
The motor current is lower than the
value in parameter H-70 Warning Current
Low.
[69]
Above I high
The motor current is higher than the
value in parameter H-71 Warning Current
High.
DET-618D