Technical Data; Degree Of Protection And Weight; Input And Output Voltage - Bosch rexroth IndraControl VAU 02.1 Operating Instructions Manual

Table of Contents

Advertisement

8/31

Technical data

7 Technical data

7.1 Degree of protection and weight

Degree of protection
Weight
Tab. 7-1: Degree of protection and weight

7.2 Input and output voltage

Nominal input voltage
Input voltage range
Current consumption at U
Current consumption (max.) at U
Max. power consumption
Tab. 7-2: Input voltage 24 V
Nominal output voltage
Current output at U
N
Bridging time
Max. output power
Short-circuit protection
Tab. 7-3: Output voltage 24 V
CAUTION
Do not short-circuit the UPS connections.
NOTICE
The max. power consumption of the connected control cabinet or panel PC must
not exceed the max. output power of the UPS of 72 W.
Bosch Rexroth AG R911384727_Edition 03
IP 20
0.94 kg
24 V DC (use a 24 V power supply unit acc. to DIN EN
60742, classification VDE 0551, for example the power sup-
ply unit VAP01.1H-W23-024-010-NN, part number
R911171065)
24 V DC +20 %, -20 %
4.2 A
N
-20% 5.2 A
N
100 W
24 V DC
3 A max.
3 minutes max. if battery charged by 50%
5 minutes max. if battery charged by 85%
72 W
Yes
Explosion hazard due to short-circuiting of the
connections
Overheating and possible damage to the UPS if
the max. power consumption is exceeded.