Electric Meters And Rates; Heating And Cooling Capacity Depending On Water Flow And Outside Temperature - Panasonic Aquarea B1 Planning And Installation Manual

Air-to-water heat pumps split systems and compact systems
Table of Contents

Advertisement

Planning

5.4.2 Electric meters and rates

For connecting heat pumps to the power grid, consent should be obtained from the competent
Energy Supply Company (EVU) and connection conditions should be requested. In this context,
data regarding the building, about the heat pump and operating mode is also to be provided. If it
is possible to utilise more favourable heat pump charges, possible cut-off times and their dura-
tion are to be requested and taken into account for planning.
The power consumption of the heat pump is measured to determine the annual performance
number and for settlement of a possibly different tariff, measured by means of one's own current
counter, to which all power connections of the heat pump are connected.
CAUTION
Danger of Water Lines Freezing Over During the Cut-off Times by EVU
If cut-off times by the Energy Supply Company (EVU) coincide with frost periods, there can be
frost damage, if the device for ensuring frost-free working is similarly affected by the cut-off time.
► Connect booster cabinet heating or other devices for frost-free working to the power
grid such that it is not affected by the cut-off times.
5.5
Heating and cooling capacity depending on water in-
flow and outside temperature
Key for the Performance Table
The values in the performance tables show the Panasonic measurement data matching with EN
14511-2. The data should be considered as reference values and do not offer any performance
guarantee.
t
: Outside temperature (°C)
a
t
: Water inflow temperature (°C)
V
P
: Heating capacity (kW)
Hzg
P
: Cooling capacity (kW)
Klg
Performances of split systems with combination hydro-module in heating mode
Aquarea LT, combination hydro-module, single- phase, heating and cooling (ADC), Generation H
WH-ADC0309H3E5(B) / WH-UD03HE5-1
t
(°C)
30
35
V
t
(°C)
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
a
Hzg
zu
Hzg
zu
Hzg
zu
25
3.20
0.42
7.62
3.20
0.46
6.96
3.20
0.55
7
3.20
0.58
5.52
3.12
0.64
4.88
3.20
0.77
2
3.20
0.82
3.90
3.29
0.90
3.66
3.20
1.03
-7
3.20
1.08
2.96
3.58
1.19
3.00
3.20
1.34
-15
3.20
1.26
2.54
3.13
1.39
2.25
3.10
1.52
WH-ADC0309H3E5(B) / WH-UD05HE5-1
t
(°C)
30
35
V
t
(°C)
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
a
Hzg
zu
Hzg
zu
Hzg
zu
25
5.00
0.74
6.76
5.00
0.82
6.10
5.00
1.02
7
5.00
0.97
5.15
5.00
1.08
4.63
5.00
1.28
2
4.20
1.22
3.44
4.20
1.35
3.11
4.20
1.50
-7
4.20
1.46
2.88
4.20
1.62
2.59
4.00
1.72
-15
4.20
1.75
2.40
4.20
1.94
2.17
3.80
1.96
116
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
P
: Power consumption (kW)
zu
COP: Performance number in heating mode
EER: Performance number in cooling mode
40
45
50
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
5.82
3.20
0.63
5.08
3.20
0.73
4.38
3.20
4.16
3.20
0.89
3.60
3.20
1.05
3.05
3.20
3.11
3.20
1.16
2.76
3.20
1.33
2.41
3.20
2.39
3.20
1.48
2.16
3.20
1.67
1.92
3.20
2.04
3.00
1.64
1.83
2.80
1.78
1.57
2.75
40
45
50
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
4.90
5.00
1.22
4.10
5.00
1.35
3.70
5.00
3.91
5.00
1.48
3.38
5.00
1.68
2.98
5.00
2.80
4.20
1.65
2.55
4.15
1.86
2.23
4.10
2.33
3.80
1.82
2.09
3.70
1.95
1.90
3.55
1.94
3.40
1.98
1.72
3.20
2.05
1.56
3.00
Aquarea LT, combination hydro-module, single- phase, heating and cooling (ADC), Generation H
WH-ADC0309H3E5(B) / WH-UD07HE5-1
t
(°C)
30
V
t
(°C)
P
(kW) P
(kW)
a
Hzg
zu
25
7.00
0.79
7
7.00
1.43
2
6.70
1.83
-7
5.15
1.80
-15
4.60
1.87
WH-ADC0309H3E5(B) / WH-UD09HE5-1
t
(°C)
30
V
t
(°C)
P
(kW) P
(kW)
a
Hzg
zu
25
9.00
1.07
7
9.00
1.93
2
6.80
1.87
-7
6.10
2.16
-15
6.00
2.55
WH-ADC1216H6E5 / WH-UD12HE5
t
(°C)
30
V
t
(°C)
P
(kW) P
(kW)
a
Hzg
zu
25
12.00
1.38
7
12.00
2.10
2
11.80
3.10
-7
10.40
3.37
-15
9.30
3.46
WH-ADC1216H6E5 / WH-UD16HE5
t
(°C)
30
V
t
(°C)
P
(kW) P
(kW)
a
Hzg
zu
25
16.00
2.31
7
16.00
3.21
2
13.50
3.74
-7
11.90
4.03
-15
10.60
4.09
Aquarea LT, Combination hydro-module, Three-phase, Heating and cooling (ADC), Generation H
WH-ADC0916H9E8 / WH-UD09HE8
t
(°C)
30
V
t
(°C)
P
(kW) P
(kW)
a
Hzg
zu
25
9.00
1.05
7
9.00
1.54
2
9.31
2.35
-7
9.35
2.91
-15
8.65
3.06
WH-ADC0916H9E8 / WH-UD12HE8
t
(°C)
30
V
t
(°C)
P
(kW) P
(kW)
a
Hzg
zu
25
12.00
1.38
7
12.00
2.10
2
11.80
3.10
-7
10.40
3.37
-15
9.30
3.46
55
(kW)
COP
zu
WH-ADC0916H9E8 / WH-UD16HE8
0.82
3.90
t
(°C)
30
V
1.20
2.67
t
(°C)
P
(kW) P
(kW)
a
Hzg
zu
1.49
2.15
25
16.00
2.31
1.86
1.72
7
16.00
3.21
1.92
1.43
2
13.50
3.74
-7
11.90
4.03
-15
10.60
4.09
55
(kW)
COP
zu
1.49
3.36
1.89
2.65
2.07
1.98
2.08
1.71
2.12
1.42
Aquarea air-to-water heat pumps - Planning and installation manual - 01/2018
35
40
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
zu
8.86
7.00
0.97
7.22
6.74
1.14
5.91
6.74
1.14
4.90
7.00
1.57
4.46
7.00
1.84
3.81
7.00
1.84
3.66
6.55
1.96
3.34
6.58
2.29
2.87
6.58
2.29
2.86
5.15
1.92
2.68
5.08
2.14
2.37
5.08
2.14
2.46
4.60
1.98
2.32
4.60
2.19
2.10
4.60
2.19
35
40
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
zu
8.41
9.00
1.26
7.14
8.66
1.48
5.87
8.66
1.48
4.66
9.00
2.18
4.13
9.00
2.49
3.62
9.00
2.49
3.64
6.70
2.14
3.13
6.65
2.38
2.79
6.65
2.38
2.82
5.90
2.34
2.52
5.85
2.61
2.24
5.85
2.61
2.35
5.90
2.66
2.22
5.65
2.82
2.00
5.65
2.82
35
40
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
zu
8.70
12.00
1.66
7.23
11.80
1.94
6.08
11.70
2.23
5.71
12.00
2.53
4.74
12.00
2.96
4.05
12.00
3.39
3.81
11.40
3.31
3.44
11.00
3.53
3.12
10.60
3.74
3.09
10.00
3.66
2.73
9.60
3.95
2.43
9.20
4.24
2.69
8.90
3.62
2.46
8.50
3.79
2.24
8.10
3.95
35
40
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
zu
6.93
16.00
2.69
5.95
16.00
3.07
5.21
16.00
3.45
4.98
16.00
3.74
4.28
16.00
4.27
3.75
16.00
4.80
3.61
13.00
3.96
3.28
12.40
4.18
2.97
11.90
4.40
2.95
11.40
4.43
2.57
10.80
4.83
2.24
10.30
5.22
2.59
10.30
4.38
2.35
10.00
4.67
2.14
9.70
4.96
35
40
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
zu
8.57
9.00
1.24
7.26
8.73
1.44
6.06
8.46
1.64
5.84
9.00
1.86
4.84
9.00
2.16
4.17
9.00
2.46
3.96
9.00
2.51
3.59
9.00
2.78
3.24
9.00
3.05
3.21
9.00
3.16
2.85
8.85
3.54
2.50
8.70
3.92
2.83
8.30
3.21
2.59
7.95
3.41
2.33
7.60
3.61
35
40
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
zu
8.70
12.00
1.66
7.23
11.80
1.94
6.08
11.70
2.23
5.71
12.00
2.53
4.74
12.00
2.96
4.05
12.00
3.39
3.81
11.40
3.31
3.44
11.00
3.53
3.12
10.60
3.74
3.09
10.00
3.66
2.73
9.60
3.95
2.43
9.20
4.24
2.69
8.90
3.62
2.46
8.50
3.79
2.24
8.10
3.95
35
40
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
Hzg
zu
Hzg
zu
Hzg
zu
6.93
16.00
2.69
5.95
16.00
3.07
5.21
16.00
3.45
4.98
16.00
3.74
4.28
16.00
4.27
3.75
16.00
4.80
3.61
13.00
3.96
3.28
12.40
4.18
2.97
11.90
4.40
2.95
11.40
4.43
2.57
10.80
4.83
2.24
10.30
5.22
2.59
10.30
4.38
2.35
10.00
4.67
2.14
9.70
4.96
Planning
45
50
55
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
Hzg
zu
Hzg
zu
5.91
6.24
1.43
4.36
6.00
1.55
3.87
3.81
6.90
2.35
2.94
6.80
2.59
2.63
2.87
6.30
2.82
2.24
6.00
3.01
1.99
2.37
4.90
2.45
2.00
4.80
2.54
1.89
2.10
4.55
2.63
1.73
4.50
2.86
1.57
45
50
55
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
Hzg
zu
Hzg
zu
5.87
8.03
1.85
4.34
7.74
2.01
3.85
3.62
8.95
3.25
2.76
8.90
3.70
2.41
2.79
6.30
2.82
2.24
6.00
3.01
1.99
2.24
5.80
2.98
1.95
5.80
3.08
1.88
2.00
5.20
3.08
1.69
5.00
3.18
1.57
45
50
55
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
Hzg
zu
Hzg
zu
5.25
11.50
2.49
4.62
11.40
2.74
4.16
3.54
12.00
3.78
3.17
12.00
4.16
2.88
2.83
9.80
3.94
2.49
9.10
4.14
2.20
2.17
8.70
4.26
2.04
8.20
4.27
1.92
2.05
7.50
4.05
1.85
7.00
4.16
1.68
45
50
55
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
Hzg
zu
Hzg
zu
4.64
16.00
3.67
4.36
15.90
3.89
4.09
3.33
15.20
5.11
2.97
14.50
5.41
2.68
2.70
10.80
4.46
2.42
9.80
4.51
2.17
1.97
9.60
5.09
1.89
9.00
4.95
1.82
1.96
8.80
4.94
1.78
7.90
4.91
1.61
45
50
55
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
Hzg
zu
Hzg
zu
5.16
8.28
1.82
4.55
8.10
2.00
4.05
3.66
9.00
2.76
3.26
9.00
3.06
2.94
2.95
8.90
3.49
2.55
8.80
3.94
2.23
2.21
8.30
3.89
2.13
7.90
3.86
2.05
2.11
7.15
3.71
1.93
6.70
3.81
1.76
45
50
55
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
Hzg
zu
Hzg
zu
5.25
11.50
2.49
4.62
11.40
2.74
4.16
3.54
12.00
3.78
3.17
12.00
4.16
2.88
2.83
9.80
3.94
2.49
9.10
4.14
2.20
2.17
8.70
4.26
2.04
8.20
4.27
1.92
2.05
7.50
4.05
1.85
7.00
4.16
1.68
45
50
55
(kW)
COP
P
(kW) P
(kW)
COP
P
(kW) P
(kW)
COP
Hzg
zu
Hzg
zu
4.64
16.00
3.67
4.36
15.90
3.89
4.09
3.33
15.20
5.11
2.97
14.50
5.41
2.68
2.70
10.80
4.46
2.42
9.80
4.51
2.17
1.97
9.60
5.09
1.89
9.00
4.95
1.82
1.96
8.80
4.94
1.78
7.90
4.91
1.61
117