Bosch Rexroth AG
Assembly, Disassembly and Electrical Installation
RS232 cable
Permitted cable lengths
Cable type
Tab. 10-7: RS232 cable, requirements
Malfunctions
NOTICE
Use only shielded cables and metallic or conductive connector/coupling covers
with large-area shield support.
NOTICE
Use short RS232 cables, if possible.
If possible, use only the cable listed in
and VAU 01.1Z" on page
Connecting the RS232 cable
1. Plug the connector of the RS232 cable into XCOM1 at the UPS.
2. Plug the female connector of the RS232 cable into a COM interface at the
panel PC or control cabinet PC.
The UPS software, which is installed on the panel PC or control cab-
inet PC, recognizes automatically the COM interface which is con-
nected to the UPS, if the software has been configured correspond-
ingly ("Enable Scan" activated).
28/53
Up to 20 m (maximum length)
Shielded, cross-section min. 0.08 mm
Malfunctions due to insufficient shielding!
Malfunctions due to too long cables!
chapter 5.3 "RS232 Cable for VAU 01.1S
8.
VAU 01.1
2
(AWG28)
DOK-SUPPL*-VAU*01.1X**-IT02-EN-P