Mains Supply 3 x 525 - 600 VAC
AF-650 GP
High/ Normal
Load*
Typical Shaft Output [kW]
Typical Shaft Output [HP] at 575V
Unit Size IP 55, 66
Unit Size IP20
Output current
Continuous
(3 x 525-550 V ) [A]
Intermittent
(3 x 525-550 V ) [A]
Continuous
(3 x 525-600 V ) [A]
Intermittent
(3 x 525-600 V ) [A]
Continuous kVA (550 V AC) [kVA]
Continuous kVA (575 V AC) [kVA]
Max. cable size IP20
(mains, motor)
2)
2
[AWG]
[mm
]
Max. cable size IP20
(load share, brake)
[AWG]
2)
[mm
2
]
Max. cable size IP21, 55, 66
(mains, motor, load share and
brake)
2)
2
[AWG]
[mm
]
Max cable size with mains discon-
nect
Max. input current
Continuous
at 550 V [A]
Intermittent
at 550 V [A]
Continuous
at 575 V [A]
Intermittent
at 575 V [A]
1)
Max. mains fuses
[A]
Environment
Estimated power loss
at rated max. load [W]
Weight,
Unit Size IP20 [kg]
Weight,
Unit Size IP 55 IP 66 [kg]
4)
Efficiency
50 HP
HD
LD
37
45
50
60
31
31
33
33
54
65
81
72
52
62
78
68
51.4
61.9
51.8
61.7
50 (1)
50 (1)
90 (3/0)
35 (2)
49
59
74
65
47
56
70
62
125
850
4)
35
45
0.98
60 HP
75 HP
HD
LD
HD
LD
45
55
55
75
60
74
75
100
31
32
33
34
65
87
87
105
98
96
131
116
62
83
83
100
93
91
125
110
61.9
82.9
82.9
100.0
61.7
82.7
82.7
99.6
95 (4/0)
70 (3/0)
59
78.9
78.9
95.3
89
87
118
105
56
75
75
91
85
83
113
100
160
250
1100
1400
35
50
45
65
0.98
0.98
AF-650 GP Design Guide
100 HP
HD
LD
75
90
100
120
32
34
105
137
158
151
100
131
4
150
144
100.0
130.5
99.6
130.5
150 (300mcm)
95 (4/0)
120 (4/0)
150 (300mcm)
95.3
124.3
143
137
91
119
137
131
250
1500
50
65
0.98
63