Pelv - Protective Extra Low Voltage - GE AF-650 GP Design Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

EMC immunity form
Voltage range: 200-240 V, 380-480 V
Basic standard
3
Acceptance criterion
Line
Motor
Brake
Load sharing
Control wires
Standard bus
Relay wires
Application and network options
Keypad cable
External 24 V DC
Enclosure
AD: Air Discharge
CD: Contact Discharge
CM: Common mode
DM: Differential mode
1. Injection on cable shield.
Table 3.2: Immunity

3.6.1 PELV - Protective Extra Low Voltage

PELV offers protection by way of extra low voltage. Protection against electric shock is ensured when the electrical supply is of the PELV type and the installation
is made as described in local/national regulations on PELV supplies.
All control terminals and relay terminals 01-03/04-06 comply with PELV (Protective Extra Low Voltage) (Does not apply to grounded Delta leg above 400 V).
Galvanic (ensured) isolation is obtained by fulfilling requirements for higher isolation and by providing the relevant creapage/clearance distances. These require-
ments are described in the EN 61800-5-1 standard.
The components that make up the electrical isolation, as described below, also comply with the requirements for higher isolation and the relevant test as described
in EN 61800-5-1.
The PELV galvanic isolation can be shown in six locations (see illustration):
In order to maintain PELV all connections made to the control terminals must be PELV, e.g. thermistor must be reinforced/double insulated.
1.
Power supply (SMPS) incl. signal isolation of U
termediate current voltage.
2.
Gate drive that runs the IGBTs (trigger transformers/opto-couplers).
3.
Current transducers.
4.
Opto-coupler, brake module.
5.
Internal inrush, RFI, and temperature measurement circuits.
6.
Custom relays.
The functional galvanic isolation (a and b on drawing) is for the 24 V back-up option and for the RS 485 standard bus interface.
38
Burst
Surge
IEC 61000-4-4
IEC 61000-4-5
B
B
2 kV/2 Ω DM
4 kV CM
4 kV/12 Ω CM
1)
4 kV CM
4 kV/2 Ω
4 kV CM
4 kV/2 Ω
1)
4 kV CM
1)
4 kV/2 Ω
2 kV CM
1)
2 kV/2 Ω
2 kV CM
2 kV/2 Ω
1)
2 kV CM
2 kV/2 Ω
1)
2 kV CM
1)
2 kV/2 Ω
1)
2 kV CM
2 kV/2 Ω
0.5 kV/2 Ω DM
2 kV CM
1 kV/12 Ω CM
, indicating the in-
DC
ESD
Radiated electromagnetic field
IEC 61000-4-2
IEC 61000-4-3
B
A
8 kV AD
10 V/m
6 kV CD
Illustration 3.3: Galvanic isolation
AF-650 GP Design Guide
RF common
mode voltage
IEC 61000-4-6
A
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS
10 V
RMS

Hide quick links: