L08 Indoor Unit Address Not Set - Panasonic 2WAY Multi Technical & Service Manual

Troubleshooting. gas heat pump, air conditioner.
Hide thumbs Also See for 2WAY Multi:
Table of Contents

Advertisement

L08 Indoor Unit Address Not Set

Error detection method
An error is determined when the indoor unit capacity is not set.
• When the indoor unit address was not set when new non-volatile memory (EEPROM) was installed.
• When indoor unit address in the remote controller detailed settings mode is "invalid."
Troubleshooting
1
Use the remote controller detailed settings mode to check indoor unit addresses (item code
Indoor unit
1-1
13) and set an indoor unit address to replace invalid (0) ones.
Set address
● See "5. Reference Document" for detailed remote controller settings.
IV–72