L07 Group Control Wire Present for Individual-Control Indoor Unit

(Cannot be detected when the water heat exchanger unit is connected.)
Error detection method
An error is determined when remote controller group wiring includes an indoor unit set for independent
operation.
• When remote controller group wiring is set up after auto-addressing is complete.
• When group settings for an indoor unit wired into a remote controller group are changed to "Independent" in
remote controller detailed settings mode.
Troubleshooting
1
1-1 Remote controller group wiring routed as intended?
Remote
controller
1-2 In the remote controller detailed settings mode, check the group settings (item code 14). If set
group wiring
to Independent (0), correct it or repeat auto-addressing process.
1-3 After repairing remote controller group wiring, repeat auto-addressing process.
● See "5. Reference Document" for detailed remote controller settings.
IV–71
Yes 1-2
No
1-3