Configuring For Network Communication Using A D6680 - Bosch Conettix D6680 Installation Instructions Manual

Ethernet network adapter
Table of Contents

Advertisement

The type(s) of peripheral reporting device(s) used
in your central station (for example external printer
or automation computer)
The supervision characteristics for these devices
The type of communicators reporting to the
receiver
The number and type of receiving lines in use
3.7
Configuring for Network
Communication Using a D6680
The following steps allow the D6600 to communicate
with the host PC running the D6200 Programming
Software using a D6680 on a network.
For the network communication to function,
install a properly configured D6680. Refer
to the previous sections. If network
communications are not installed, further
D6200 software programming using the
network is not possible.
1. On the D6600 keypad, press [M/E] and enter the
default passcode of [6][6][0][0] to enter the
programming mode. Press [M/E] again.
To change any programming parameter,
follow this syntax:
Press [M/E],
Enter the desired value,
Press [M/E] again to store the value.
2. Scroll down to 6 NETWORK CONFIGURATION
and press [M/E].
3. Scroll down to 6.1 COM4 Network Adapter
and press [M/E].
4. Verify that 6.1.1 COM4 Baud Rate is set to a
value of 9 and press [M/E].
Bosch Security Systems, Inc. | 5/07 | 4998138732-01
Conettix D6680 | Installation Instructions | 3.0 Configuration and Programming
Available from A1 Security Cameras
www.a1securitycameras.com email: sales@a1securitycameras.com
5. Verify that 6.1.2 COM4 Data Bit is set to 8
(default) and press [M/E]. If necessary, change the
value to 8
6. Verify that section 6.1.3 COM4 Parity is set
to 0 (default) and press [M/E]. If necessary, change
the value to 0.
7. Verify that section 6.1.4 COM4 Stop Bit is set
to 1 (default) and press [M/E]. If necessary, change
the value to 1.
8. Set 6.1.5 COM4 Network Adapter Enabled
to a value of 1 and press [M/E]. If the value is not
1, press [M/E][1][M/E].
9. If the D6680 connected to COM4 has encryption
enabled, Set 6.1.6 COM4 Network
Encryption Enabled to 1.
If you did not install the optional D6672
Serial COM1 expansion kit, skip step 10.
10. If you installed COM1, press [CAN][▼]. Repeat
steps 4 through step 9 for
6.2 COM1 Network Adapter.
11. Press [CAN] and scroll down to
6.3 Automation Network Connection.
12. Press [M/E] twice.
13