Prevention of unexpected start-up (option +Q957)
for ACS880-07/17/37 drives

Advertisement

Table of Contents
loading

Summary of Contents for ABB ACS880-07

  • Page 1 Options for ABB drives User’s manual Prevention of unexpected start-up (option +Q957) for ACS880-07/17/37 drives...
  • Page 2: List Of Related Manuals

    List of related manuals Drive hardware manuals and guides Code (English) ACS880-07 drives (560 to 2800 kW) hardware manual 3AUA0000143261 ACS880-07 drives (45 to 630 kW, 50 to 700 hp) 3AUA0000105718 hardware manual ACS880-17 drives (160 to 3200 kW) hardware manual 3AXD50000020436...
  • Page 3 User’s manual Prevention of unexpected start-up (option +Q957) for ACS880-07/17/37 drives Table of contents  2018 ABB Oy. All Rights Reserved. 3AUA0000119910 Rev F EFFECTIVE: 2018-02-02...
  • Page 5: Table Of Contents

    Table of contents List of related manuals ........... 2 1.
  • Page 6 ACS880-07 drives, frames R6 to R11 ....... . . 22...
  • Page 7: Introduction To The Manual

    This chapter describes the manual in short and gives some general information for the reader. The chapter also contains a quick reference for implementing a safety system. Applicability The manual applies to ACS880-07/17/37 drives which have the option: Prevention of unexpected start-up (option +Q957). Safety instructions Only a qualified electrician who has appropriate knowledge on functional/machine/process safety is allowed to install, start up and maintain the safety circuit.
  • Page 8: Target Audience

    8 Introduction to the manual WARNING! Frames nxDXT + nxR8i: The Safe torque off functionality is only achieved through the XSTO connector of the inverter control unit. True Safe torque off functionality is not achieved through the XSTO connectors of the supply control unit.
  • Page 9: Abbreviations

    EN/IEC 62061 Exclusion of liability ABB is not responsible for the implementation, verification and validation of the overall safety system. It is the responsibility of the system integrator (or other party) who is responsible for the overall system and system safety.
  • Page 10: Quick Reference Guide For Implementing A Safety System

    If you select EN/IEC 62061 or IEC 61511, make a safety plan. See EN/IEC 62061 or IEC 61511. Assess safety: analyze and evaluate risks (estimate SIL/PL) and define risk reduction strategies. Define the safety requirements. Design the safety system. The part of the design made by ABB is described in chapter Option description and instructions on page 11.
  • Page 11: Option Description And Instructions

    Option description and instructions 11 Option description and instructions Contents this chapter This chapter describes the +Q957 Prevention of unexpected start-up option and instructs how to wire, start up, test, validate, use and maintain it. The safety data is also given. Overview The Prevention of unexpected start -up (POUS) function disables the control voltage of the power semiconductors of the drive (inverter) output stage.
  • Page 12 For more information on the emergency stop function, see the appropriate user’s manual. Note: ACS880-07 drives, frames nxDXT + nxR8i with a main contactor/breaker (option +F250/+F255), ACS880-17/37 drives, frames nxR8i + nxR8i, and ACS880-17/37 drives, frames R8 and R11: When the STO function is activated in the inverter unit, the main contactor/breaker is opened after a user-defined delay (defined with parameter 94.11, the...
  • Page 13: Operation Principle

    Option description and instructions 13 Operation principle -T22 Control relays Drive control board 24 V -A41 XSTO SGND -A65 -Sxx -X969 -Pxx Reset (automatic) POUS safety relay POUS switch (user-defined) Control board (inverter unit) POUS indication lamp (user-defined) 24 V power supply X969 STO terminal block The dash-dot (...
  • Page 14: Fault Reaction Function

    31.22 STO indication run/stop is set to value Warning/Warning (recommended). Additional parameter settings for ACS880-07 drives, frames nxDXT + nxR8i and ACS880-17/37 drives, frames nxR8i + nxR8i Note: ACS880 primary control program controls the inverter unit by default. There are dedicated control boards for the supply and inverter units.
  • Page 15: Wiring

    Option description and instructions 15 Wiring The operating switch and the indication lamp for the POUS function are not factory- installed. The user must install and wire them to the drive on site. There are double contacts in the POUS switch [Sxx] and double wiring (two-channel connection) between the button and the POUS safety relay [A65].
  • Page 16: Start-Up And Acceptance Test

    16 Option description and instructions Start-up and acceptance test You need the Drive composer PC tool or a control panel to perform the start-up and acceptance test. Initial status: Make sure that the drive is ready for use, that is, you have done the tasks of the drive start-up procedure.
  • Page 17 Option description and instructions 17 Action Switch off the drive start signal. If a fault message is generated, reset the drive. See section POUS indications on page 18. Restart the drive and motor and check that they operate normally. Fill in and sign the acceptance test report which verifies that the safety function is safe and accepted to operation.
  • Page 18: Use Of The Safety Function

    If you change any wiring or component after the start up, or restore parameters to their default values: • Use only ABB approved spare parts • Register the change to the change log for the safety circuit •...
  • Page 19: Proof Test Interval

    Option description and instructions 19 Proof test interval  After the operation of the safety function is validated at start-up, the safety function must be maintained by periodic proof testing. In high demand mode of operation, the maximum proof test interval is 20 years. In low demand mode of operation, the maximum proof test interval is 2 or 5 years (high or low demand as defined in IEC 61508, EN/IEC 62061 and EN ISO 13849-1).
  • Page 20: Safety Data

    Safety data The safety data given below is valid for the default design of the safety circuit. In case the final design differs from the default, ABB calculates new safety data and delivers it separately to the customer. Safety data values ...
  • Page 21: Relevant Failure Modes

    Option description and instructions 21 Relevant failure modes  Internal failures of safety relays and STO. These failures are included in the PFH value of the function. Fault exclusions  Fault exclusions (not considered in the calculations): • any short and open circuits in the cables of the safety circuit •...
  • Page 22: Competence

    For the environmental limits for the safety functions and the drive, refer to the hardware manual. ACS880-07 drives, frames R6 to R11 The maximum ambient temperature for the drive with safety relays is 45 °C (113 °F). In the temperature range +40…45 °C (+104…113 °F), the rated output current must be derated by 2% for every added 1 °C (1.8 °F).
  • Page 23: Related Standards And Directives

    Option description and instructions 23 Related standards and directives Standard Name EN 60204-1:2006 + AC:2010 Safety of machinery – Electrical equipment of machines – Part 1: General IEC 60204-1:2016 requirements IEC 61508-1:2010 Functional safety of electrical/electronic/programmable electronic safety- related systems - Part 1: General requirements. IEC 61508-2:2010 Functional safety of electrical/electronic/programmable electronic safety- related systems - Part 2: Requirements for electrical/electronic/...
  • Page 24 24 Option description and instructions...
  • Page 25: Product And Service Inquiries

    Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
  • Page 26 Contact us www.abb.com/drives www.abb.com/drivespartners 3AUA0000119910 Rev F (EN) 2018-02-02...