CHAPTER 6: METERING

Directional Power

845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
Phase B Demand (K2 Ph B Demand) 0.000 A
Range: 0.000 to 12000.000 A
Phase C Demand (K2 Ph C Demand) 0.000 A
Range: 0.000 to 12000.000 A
Maximum Phase A Demand (K2 Max Ph A Demand) 0.000 A
Range: 0.000 to 12000.000 A
Maximum Phase B Demand (K2 Max Ph B Demand) 0.000 A
Range: 0.000 to 12000.000 A
Maximum Phase C Demand (K2 Max Ph C Demand) 0.000 A
Range: 0.000 to 12000.000 A
Date/Time Phase A Demand (K2 Date/Time Ph A Demand) MM/DD/YY HH:MM:SS
Default: 01/01/70 00:00:00
Date/Time Phase B Demand (K2 Date/Time Ph B Demand) MM/DD/YY HH:MM:SS
Default: 01/01/70 00:00:00
Date/Time Phase C Demand (K2 Date/Time Ph C Demand) MM/DD/YY HH:MM:SS
Default: 01/01/70 00:00:00
Path:
Metering > Directional Power
The effective operating quantities of the sensitive directional power elements are displayed
here. The display may be useful to calibrate the feature by compensating the angular
errors of the CTs and VTs with the use of the RCA and CALIBRATION settings.
Directional Power 1 (Directional Power 1) 0.0 kW
Range: -214748364.8 kW to 214748364.7 kW
Directional Power 2 (Directional Power 2) 0.0 kW
Range: -214748364.8 kW to 214748364.7 kW
DIRECTIONAL POWER
6–17