DNP IMPLEMENTATION
OBJECT
OBJECT
VARIATION
DESCRIPTION
NO.
NO.
30
0
Analog Input
(Variation 0 is used
to request default
variation)
1
32-Bit Analog Input
2
16-Bit Analog Input
3
32-Bit Analog Input
without Flag
4
16-Bit Analog Input
without Flag
5
short floating point
32
0
Analog Change
Event (Variation 0 is
used to request
default variation)
1
32-Bit Analog
Change Event
without Time
2
16-Bit Analog
Change Event
without Time
3
32-Bit Analog
Change Event with
Time
4
16-Bit Analog
Change Event with
Time
5
short floating point
Analog Change
Event without Time
7
short floating point
Analog Change
Event with Time
34
0
Analog Input
Reporting Deadband
(Variation 0 is used
to request default
variation)
1
16-bit Analog Input
Reporting Deadband
(default - see Note 1)
2
32-bit Analog Input
Reporting Deadband
4-10
REQUEST
FUNCTION
QUALIFIER CODES (HEX) FUNCTION CODES
CODES (DEC)
1 (read)
00, 01 (start-stop)
22 (assign class)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
22 (assign class)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
22 (assign class)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
22 (assign class)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
22 (assign class)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
22 (assign class)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
2 (write)
00, 01 (start-stop)
07, 08 (limited quantity)
17, 28 (index)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 4: DNP 3
RESPONSE
QUALIFIER CODES
(DEC)
(HEX)
---
---
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
---
---
129 (response)
17, 28 (index)
130 (unsol. resp.)
129 (response)
17, 28 (index)
130 (unsol. resp.)
129 (response)
17, 28 (index)
130 (unsol. resp.)
129 (response)
17, 28 (index)
130 (unsol. resp.)
129 (response)
17, 28 (index)
130 (unsol. resp.)
129 (response)
17, 28 (index)
130 (unsol. resp.)
---
---
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
---
---
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents