The BA/T100 units are 4 to 20mA loop powered transmitters that can be ordered with separately purchased 100Ω (385) platinum
RTD. The BA/T1K units are 4 to 20mA loop powered transmitters that can be ordered with separately purchased 1KΩ (385)
platinum RTD. The BA/T10K units are 4 to 20mA loop powered or 0 to 5VDC or 0 to 10VDC transmitters that can be ordered
with separately purchased 10K-2, 10KΩ type 2 thermistors. T100 and T1K transmitters come with flying leads but terminals are
available (-TS). Terminals are not available on the T10K units.
6
Identification
Fig 1: BA/T1x-XOR-TS
Transmitter w/ plate mount
Fig 3: BA/T1x-XOR-TRK
Transmitter w/ Snaptrack
Fig 5: BA/T1x-XOR-BB2
Transmitter in BAPI-Box 2 (BB2)
Fig 7: BA/T1x-XOR-(EU, EUO)
Transmitter in Weather Tight (EU) Enclosure
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com
BA/(T100, T1K, T10K) Temperature Transmitters
Transmitter only (fits inside Weather Tight (EU) Enclosure
Specifications subject to change without notice.
Temperature Sensor Transmitters
Installation & Operating Instructions
Peel off
mounting tape
Fig 2: BA/T1x-XOR-STM-TS
Transmitter only
Fig 4: BA/T1x-XOR-BB
Transmitter in BAPI-Box (BB)
Fig 6: BA/T1x-XOR-WP
Transmitter in Weatherproof (WP) Enclosure
Fig 8: BA/T1x-XOR-EUM
rev. 04/18/13
1 of 4

Advertisement

loading

Summary of Contents for BAPI BA/T100

  • Page 1 Overview The BA/T100 units are 4 to 20mA loop powered transmitters that can be ordered with separately purchased 100Ω (385) platinum RTD. The BA/T1K units are 4 to 20mA loop powered transmitters that can be ordered with separately purchased 1KΩ (385) platinum RTD.
  • Page 2 BAPI-Box (BB) Enclosure Fig 13: BA/T1x-XOR-BB2-TS Fig 14: BA/T1x-XOR-WP-TS Fig 15: BA/T1x-XOR-(EU, EUO) in BAPI-Box 2 (BB2) Enclosure in Weatherproof (WP) Enclosure in Weather Tight (EU) Enclosure Specifications subject to change without notice. Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA Tel:+1-608-735-4800 •...
  • Page 3 All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s wiring in the same conduit as high or low voltage AC power wiring. BAPI’s tests show that inaccurate signal levels are possible when AC power wiring is present in the same conduit as the sensor wires.
  • Page 4 ±0.125% of span BAPI-Box: XOR-BB, w/ four ½” NPSM & one ½” drill-out Power Output Shift: ±0.009% of span BAPI-Box 2: XOR-BB2, w/ three ½” NPSM & three ½” drill-outs RTD Sensor: 2 wire Platinum (Pt), 385 curve Weather Tight: XOR-EU, XOR-EUO, w/ two ½” knock-outs Transmitter Ambient -4 to 158ºF(-20 to 70ºC)

This manual is also suitable for:

Ba/t1kBa/t10k