LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998 For Technical advice & Servicing contact - +44 (0) 1268 56 3256 This publication is issued to provide outline information only and is not deemed to form part of any offer or contract Our policy is one of continual improvement and we reserve the right to vary details without prior notice.
INSTALLATION INFORMATION CONNECTING THE MAINS & BATTERY 2.1 Connect mains wiring to terminal block in the back box as General marked. Note: AN EARTH CONNECTION MUST BE Installation of this product must be carried out using the MADE TO THE TERMINAL BLOCK AS MARKED. information given in this leaflet by a qualified electrician.
Auxiliary 24V Supply This is specifically not for fire protection devices. 50mA maximum. Nominal Voltage 25.3V (+2.7V / -1V) Fuse rating - F125mA Auxiliary Relay Volt free change over contacts rated at 1A 30VDC Fuse Rating 1A Note, the Auxiliary relay is configured as a fault relay, as standard (EN54 requirement), however the relay can be configured as an auxiliary fire relay, by moving a jumper link from the fault position to the fire position on the back of the PCB.
DISABLEMENT AND TEST FUNCTIONS: - Test Zone – This feature allows one person to check the detectors and sounders without having to return to the panel during the testing routine. When the appropriate zone is in test mode and a detector is activated, the sounder circuit/s will operate for a few seconds and then automatically reset.
Page 7
),5(3$1(//2*%22. SITE NAME ......SITE ADDRESS ....PERSON RESPONSIBLE... DATE SYSTEM INSTALLED BY..TELEPHONE DATE INSTALLED ..... DATE COMMISSIONED MAINTAINED UNDER CONTRACT BY SERVICE CONTRACT No. UNTIL TYPE & QTY LOCATION No DETECTOR CALL POINT SOUNDER ZONE 1 ZONE 2 For Technical advice &...