Parmet GP-300 Installation And Service Manual

Gas fired warm air heaters 300,000 to 800,000 btu/h

Advertisement

Quick Links

1
INSTALLATION AND SERVICE MANUAL
Section
1
2
3
4
5
6
7
8
9
10
THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURERS INSTRUCTIONS AND THE REGULATIONS IN FORCE AND
ONLY USED IN A SUITABLY VENTILATED LOCATION. READ THE INSTRUCTIONS
FULLY BEFORE INSTALLING OR USING THIS APPLIANCE WHICH MUST BE
INSTALLED BY A CORGI APPROVED ENGINEER
PARMET GP300/500/900
Contents
Title
Appendix A- Wiring Diagrams
Appendix B Burner Data
1
Page
2
2
2
...2
...3
4
4
5
5
6

Advertisement

loading

Summary of Contents for Parmet GP-300

  • Page 1: Table Of Contents

    INSTALLATION AND SERVICE MANUAL PARMET GP300/500/900 Contents Section Title Page Introduction Location Positioning the Unit Combustion and Ventilation Requirements ...2 Flues ...3 Gas Pipe Connection Electrical Connections Commissioning Instructions Maintenance Instructions Users Instructions Appendix A- Wiring Diagrams Appendix B Burner Data...
  • Page 2: Introduction

    A full unobstructed return air path should be provided to enable the air to return to the heater. The Parmet Range of Gas Fired Warm Air Heaters covers applications with outputs 3. Positioning the Unit from 300,000 to 800,000 Btu/h.
  • Page 3: Flues

    60 Kw) GP800 1100CM (b) Heaters installed in a plant room. Position of Air Vent HIGH Low level 540cm2 +4.5cm2/kW GP300 820CM2 1640CM2 in excess of 60 kW (83.7in2 + 0.7in2/kW in excess of 60 kW) GP400 1100CM2 2200CM2 High Level 270cm2 + 2.25cm2/kW...
  • Page 4: Gas Pipe Connection

    Model Flue Size (Nominal Bore) GP-300 230mm (9 in) GP-400 230mm (9 in) GP-500 230mm (9 in) GP-750 255mm (10 in) GP-900 255mm (10 in) Wherever possible horizontal runs should be avoided, but where this is unavoidable every one foot of horizontal flue must be followed by three feet of vertical.
  • Page 5: Commissioning Instructions

    subjected to local heat gain e.g.in front of will occur each time the external control windows allowing the sun to act directly on circuit is completed. the thermostat. With all the controls on and the thermostat Note: The main electric supply should be calling for heat, the burner starts up going protected by a fused isolating switch rated through a pre-purge period before ignition...
  • Page 6: Users Instructions

    Before commencing maintenance, isolate the unit from electricity supply. 5. The sequence of events is:- Check and clean the main fan and vent and (1) Burner fans start. housing. Check there is no impingement of (2) Air pressure switch made. the housing.

This manual is also suitable for:

Gp-500Gp-400Gp-750Gp800Gp-900