Installation Manual of Room Air Conditioner

1.Driver
2.Hacksaw
3.Hole core drill
4.Spanner(17,19 and 26mm)

Accessory parts

No.
Accessory parts
1
Remote controller
2
R-03 dry battery
3
Mounting plate
4
Drain hose
5
Steel nail, cement
6
4X25
Plastic cap
Screw
7
Drain-elbow
Cover
8
Cushion
9
10
Pipe supporting plate
11
Connecting cable
Note:Cooling only units don't have Drain-elbow
No.0010518787
Necessary Tools for Installation
5.Torque wrench(17mm,22mm,26mm)
6.Pipe cutter
7.Flaring tool
8.Knife
Drawing for the installation of indoor and outdoor units
Number
of
articles
1
Optional parts for piping
Mark
Parts name
2
A
Non-adhesive tape
Adhesive tape
B
1
C
Saddle(L.S) with screws
Connecting electric cable
D
for indoor and outdoor
1
Drain hose
E
F
Heating insulating material
4X50
6
Piping hole cover
G
4
1
Arrangement of piping directions
1
Left
4
1
1
Read this manual before installation
Explain sufficiently the operating means to the user
according to this manual.
Rear left
Rear
right
Right
Below
The marks from
A
to
The distance between the indoor unit and the floor should be
more than 2m.
9.Nipper
10.Gas leakage detector or
soap-and-water solution
11.Measuring tape
Attention must be paid to
the rising up of drain hose
in the figure are the parts numbers.
G
12.Reamer
A
C
D
E

Advertisement

loading

Summary of Contents for Haier HSU-09LEK13

  • Page 1: Installation Manual Of Room Air Conditioner

    Installation Manual of Room Air Conditioner Read this manual before installation Explain sufficiently the operating means to the user according to this manual. Necessary Tools for Installation 1.Driver 5.Torque wrench(17mm,22mm,26mm) 9.Nipper 12.Reamer 2.Hacksaw 6.Pipe cutter 10.Gas leakage detector or 3.Hole core drill 7.Flaring tool soap-and-water solution 4.Spanner(17,19 and 26mm)
  • Page 2 113.5 113.5 Floor fixing dimensions Floor fixing dimensions Floor fixing dimensions of the outdoor unit of the outdoor unit of the outdoor unit (Unit:mm) HSU-24LK2S3 (Unit:mm) HSU-09LEK13 (Unit:mm) HSU-24LEK13 HSU-09LEK03/ (DB) HSU-12LEK13 HSU-24LEE12 HSU-18LEK03-Y6 HSU-12LEK03/ (DB) HSU-09LB11 HSU-09HEG03 HSU-22LB11 HSU-24LEW12...
  • Page 3 3G1.0mm -mod 3G2.0mm 4G0.75mm 4G0.75mm HSU-05LEK03-Y Indoor unit Outdoor unit HSU-12LD11T HSU-24LD11T POWER Indoor unit HSU-09CK2S3 HSU-12LB11T HSU-12LEK03-Y3 HSU-24LEK03-Y3 Indoor unit HSU-09LEK13 HSU-09LEK03-Y3 HSU-24LEK13 HSU-12LD11 HSU-22LD11 HSU-24LEK03-Y4 HSU-12LEK13 HSU-12LEK13-M Outdoor unit HSU-09LB11 HSU-22LB11 HSU-24 LK2S2 HSU-24LEG03(T3) HSU-07LEK03 HSU-24LEK03 HSU-24LEK03-Y2 HSU-09LD11...
  • Page 4: Connection Of Pipes

    Outdoor unit Outdoor unit 1.Connection of pipes To bend a pipe, give the roundness as large as possible not to crush the pipe Connecting the pipe of gas side first makes working easier. The max vertical distance between the indoor unit and the outdoor unit is 5 m. Forced fastening without careful centering Half union Flare nut...