APPLICATION
The T841A Heating-Cooling SUPER TRADELINE®
Thermostat provides 24 Vac control of two-stage heating
and one-stage cooling in heat pump systems, using
manual changeover. This thermostat provides SYSTEM
switch selections of EM. HEAT-HEAT-OFF-COOL and
FAN switch selections of AUTO-ON. See Fig. 1. The
adjustable second stage heat anticipator allows replace-
Model
LEDs
a
T841A
EM. HEAT
,
AUX. HEAT
a
EM. HEAT LED also indicates compressor malfunction.
FRONT OF DEVICE
HEAT PUMP THERMOSTAT
EM. HEAT HEAT OFF COOL
SYSTEM
SWITCH
®U.S. Registered Trademark
Copyright © 1997 Honeywell Inc. •
®
Table 1. T841A SUPER TRADELINE® Specifications.
Heat
Changeover
Anticipation
Manual Cool
Stage Two
or Heat
Adjustable
90
90
80
80
70
70
60
60
FAN
AUTO
ON
EM. HEAT AUX. HEAT
FAN
SWITCH
Fig. 1. External view of T841A.
• All Rights Reserved
T841A Heating-Cooling
Heat Pump Thermostat
ment of most T841A models. See Table 1 for T841A
SUPER TRADELINE® specifications.
Test holes are provided on the front of the thermostat to
accommodate test meter probes without removing the
thermostat from the wall. Remove the cover of the
thermostat to expose the test holes, which are labeled to
correspond with the terminals on the back of the thermo-
stat.
Terminal
SYSTEM
Designations
Switch
W
, O,G,R,E,
EM. HEAT,
3
HEAT, OFF,
X,W
,B,Y
2
COOL
COVER
SETPOINT
SCALE
THERMOMETER
LEDS
MOUNTING
HOLES (4)
X-XX UL
INSTALLATION INSTRUCTIONS
Auto Fan in
EM. HEAT
Yes
Replaces
most T841As.
BACK OF DEVICE
WIRING TERMINAL (UP TO 12)
Remarks
M12193
69-1083

Advertisement

loading

Summary of Contents for Honeywell SUPER TRADELINE T841A

  • Page 1 T841A Heating-Cooling Heat Pump Thermostat SUPER TRADELINE ® INSTALLATION INSTRUCTIONS ment of most T841A models. See Table 1 for T841A APPLICATION SUPER TRADELINE® specifications. The T841A Heating-Cooling SUPER TRADELINE® Test holes are provided on the front of the thermostat to...
  • Page 2 Can cause electrical shock or equipment damage. When Installing this Product… The T841A can be mounted directly to a wall or horizontal 1. Read these instructions carefully. Failure to follow outlet box. Choose the method that best fits your installa- them could damage the product or cause a hazard- tion.
  • Page 3: Heat Anticipator Setting

    POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M12195 Fig. 2. Internal schematic and typical wiring diagram for SUPER TRADELINE® T841A with AUX. HEAT, EM. HEAT LEDs. Provides heat or cool changeover relay control and automatic fan in emergency heat mode.
  • Page 4 T841A HEATING-COOLING HEAT PUMP THERMOSTAT NOTE: To prevent compressor short cycling, a minimum- off timer may be included to prevent the com- pressor from starting for up to five minutes from when the thermostat last turned the compressor off, or from when the system first received power.