Z-Com SRZ IMS01T05-E2 Installation Manual

Advertisement

Quick Links

Module Type Controller SRZ
Installation
Z-COM
Communication
Manual
Extension Module
All Rights Reserved, Copyright  2006, RKC INSTRUMENT INC.
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please
place this manual in a convenient location for easy reference.
This manual describes the mounting, wiring and specifications only. For the basic operations, see
Z-COM PLC Communication Quick Instruction Manual (IMS01T14-E ), Z-COM PLC
Communication Data List (IMS01T15-E ) and Z-COM Host Communication Quick Instruction
Manual (IMS01T09-E ). For the detail handling procedures and various function settings, please
refer to separate Z-COM Instruction Manual (IMS01T07-E ).
The above manuals can be downloaded from our website:
URL: http://www.rkcinst.com/english/manual_load.htm
Accessories check
Z-COM Installation Manual (This manual) ........................................................................ 1
Z-COM PLC Communication Quick Instruction Manual (IMS01T14-E )....................... 1
Z-COM PLC Communication Data List (IMS01T15-E ) ................................................. 1
Z-COM Host Communication Quick Instruction Manual (IMS01T09-E ) ...................... 1
Joint connector cover (KSRZ-517A).................................................................................. 2
Power terminal cover (KSRZ-518A).................................................................................. 1
Safety precautions
!
WARNING
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals,
etc. to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
CAUTION
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply, source
of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
If input/output or signal lines within the building are longer than 30 meters.
If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All high-voltage
connections such as power supply terminals must be enclosed in the instrumentation panel to
avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or
equipment.
All wiring must be in accordance with local codes and regulations.
To prevent instrument damage or failure, protect the power line and the input/output lines from
high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid electric
shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock,
fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front panel
with a hard object.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made
by imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some
components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes
no warranty expressed or implied, with respect to the accuracy of the information. The information
in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior
written approval from RKC.
The Z-COM module joins with functional modules (Z-TIO, Z-DIO modules) and performs PLC
communication and host communication. The combination of Z-COM module and functional module
is called an SRZ unit.
Host computer
Z-COM module
IMS01T05-E2
Host communication
Programmable controller
PLC communication
Power supply 24 V DC
1. PARTS DESCRIPTION
Module mainframe
Address setting switch
Indication lamp (FAIL/RUN)
Loader communication
connector
Indication lamp (RX1/TX1)
Communication port
COM. PORT1
Communication 1
COM. PORT2
Indication lamp (RX2/TX2)
Communication port
COM. PORT3
Communication 2
COM. PORT4
Indication lamp
FAIL/RUN
When normal:
A green lamp is on (RUN)
[Green or Red]
Self-diagnostic error:
A green lamp flashes (FAIL)
Instrument abnormality:
A red lamp is on (FAIL)
RX1/TX1
The green lamp is lit when data corresponding to communication 1
[Green]
(COM. PORT1/COM. PORT2) is sent or received.
RX2/TX2
The green lamp is lit when data corresponding to communication 2
[Green]
(COM. PORT3/COM. PORT4) is sent or received.
Communication port (modular connector) and Communication connector
COM. PORT1
Used to connecting the Operation panel or Host computer.
(Communication 1)
COM. PORT2
The COM. PORT2 is used for the extension of the SRZ unit.
(Communication 1)
COM. PORT3
Used to connecting the programmable controller (PLC), Operation
(Communication 2)
panel or Host computer.
COM. PORT4
The COM. PORT4 is used for the extension of the SRZ unit.
(Communication 2)
Loader
This is a connector to be connected to converter and personal
communication
computer when loader communication is performed.
connector
Switch
Address setting
Set unit address of SRZ unit with address setting switch.
switch
• Sets communication speed, communication protocol and data bit
DIP switch
configuration corresponding to each of communication 1 and
communication 2.
• Sets dip switch setting validity/invalidity.
Base
Mounting holes (M3 screw)
Holes for screws to fix the base
to a panel, etc.
Customer must provide the M3
screws.
1 2
Mounting bracket
Used to fix the module on
3 4 5
DIN rails and also to fix
each module joined together.
2. MOUNTING
!
SRZ unit
To prevent electric shock or instrument failure, always turn off the
power before mounting or removing the instrument.
2.1 Mounting Cautions
(1) This instrument is intended to be used under the following environmental conditions.
(IEC61010-1) [OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
Z-TIO and Z-DIO modules
(2) Use this instrument within the following environment conditions.
• Allowable ambient temperature:
−10 to +50 °C
• Allowable ambient humidity:
5 to 95 % RH
(Absolute humidity: MAX. W. C 29.3 g/m
• Installation environment conditions: Indoor use
Altitude up to 2000 m
(3) Avoid the following conditions when selecting the mounting location:
• Rapid changes in ambient temperature which may cause condensation.
• Corrosive or inflammable gases.
• Direct vibration or shock to the mainframe.
• Water, oil, chemicals, vapor or steam splashes.
• Excessive dust, salt or iron particles.
• Excessive induction noise, static electricity, magnetic fields or noise.
Z-COM module (Right side view)
• Direct air flow from an air conditioner.
• Exposure to direct sunlight.
• Excessive heat accumulation.
(4) Take the following points into consideration when mounting this instrument in the panel.
• Ensure at least 50 mm space on top and bottom of the instrument for maintenance and
environmental reasons.
• Do not mount this instrument directly above equipment that generates large amount of heat
(heaters, transformers, semi-conductor functional devices, large-wattage resistors).
• If the ambient temperature rises above 50 °C, cool this instrument with a forced air fan, cooler, or
DIP switch
the like. However, do not allow cooled air to blow this instrument directly.
• In order to improve safety and the immunity to withstand noise, mount this instrument as far
away as possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment:
Do not mount within the same panel.
Power lines:
Separate at least 200 mm.
Rotating machinery:
Separate as far as possible.
Be sure the Z-COM module and functional modules (Z-TIO, Z-DIO) are joined when using them.
OFF
ON
Bottom
(5) This instrument is Permanently connected to equipment, please take the following points.
• A switch or circuit-breaker shall be included in the building installation.
• It shall be in close proximity to the equipment and within easy reach of the operator.
• It shall be marked as the disconnecting device for the equipment.
2.2 Joining Each Module
Before joining the Z-COM module and functional modules, use the DIP
[RS-485 or RS-422A]
switches to make the communication settings. For the setting procedure, see
Z-COM PLC Communication Quick Instruction Manual (IMS01T14-E ).
[RS-485 or RS-422A]
The maximum number of functional modules (Z-TIO-A/B, Z-DIO) described in the following can be
joined per Z-COM module. For details on joining functional modules with the Z-COM module, see
[RS-485 or RS-422A]
the Z-TIO INSTRUCTION MANUAL (IMS01T01-E ).
[RS-485 or RS-422A]
• When joining functional modules of the same type:
• When joining functional modules of two or more different types: Up to 31 modules
(However, the maximum joinable number of functional modules of the same type is 16.)
[Example] When the Z-TIO-A/B and Z-DIO modules are joined
Z-COM module
16 Z-TIO-A/B modules
Joint connector
Functional modules: Up to 31 modules
Used to mechanically and
electrically connect
When the number of correspondence channels is specified using the model code, only the
each module.
amount of data corresponding to the specified number of channels can be sent or received
(PLC communication only).
The number of the
Power supply terminals
correspondence
Z-TIO-A/B module
These are terminals to supply
channels
power to the Z-COM module
or joined function modules.
64 channels
(However, up to 16 modules)
48 channels
(However, up to 16 modules)
Terminal 3, 4 and 5
32 channels
These terminals cannot be
used for the Z-COM module.
16 channels
(Usage is prohibited.)
2.3 Dimensions
WARNING
3
dry air at 101.3 kPa)
Space required between each
module vertically
When the module is mounted on the panel,
allow a minimum of 50 mm at the top and
bottom of the module to attach the module
to the mainframe.
Procedure for mounting or removing
The procedure for mounting or removing the Z-COM module is the same as that of the function
module (Z-TIO or Z-DIO). Both DIN rail mounting and screw mounting are available.
For details on module mounting or removing, see the Z-TIO INSTRUCTION MANUAL
(IMS01T01-E ).
3. WIRING
Top
To prevent electric shock or instrument failure, do not turn on the
power until all the wiring is completed.
3.1 Wiring Cautions
• To avoid noise induction, keep communication signal wire away from instrument power line, load
lines and power lines of other electric equipment.
• If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter.
− Shorten the distance between the twisted power supply wire pitches to achieve the most
effective noise reduction.
− Always install the noise filter on a grounded panel. Minimize the wiring distance between the
noise filter output and the instrument power supply terminals to achieve the most effective
noise reduction.
− Do not connect fuses or switches to the noise filter output wiring as this will reduce the
effectiveness of the noise filter.
• Power supply wiring must be twisted and have a low voltage drop.
• For an instrument with 24 V power supply, supply power from a SELV circuit.
Up to 16 modules
• A suitable power supply should be considered in the end-use equipment.
The power supply must be in compliance with a limited-energy circuits (maximum available
current of 8 A).
• Supply the power to only one of the joined modules. When power is supplied to any one of the
joined modules, all of the joined modules will receive power.
• Select the power capacity which is appropriate for the total power consumption of all joined
SRZ unit
modules and the initial current surge when the power is turned on.
Power consumption (at maximum load):
• When connecting the wiring to the power supply terminals on the base, use the specified
solderless terminals. Only these specified solderless terminals can be used due to the insulation
between the terminals.
Screw Size: M3 × 7 (with 5.8 × 5.8 square washer)
Recommended tightening torque: 0.4 N・m (4 kgf・cm)
Applicable wire: Solid/twisted wire of 0.25 to 1.65 mm
15 Z-DIO modules
Specified solderless terminal:
Manufactured by J.S.T MFG CO., LTD.
Circular terminal with isolation V1.25−MS3
(M3 screw, width 5.5 mm, hole diameter 3.2 mm)
3.2 Terminal Configuration
Base
Z-DIO module
1
2
64 channels
128 channels
(Up to 16 modules)
48 channels
96 channels
3
4
(Up to 12 modules)
64 channels
32 channels
(Up to 8 modules)
32 channels
16 channels
(Up to 4 modules)
(Unit: mm)
76.9
30
6.7
Depth for communication cables mount
type module
Space for communication cables must be
considered when installing.
(Unit: mm)
76.9
Approx. 50
Communication
cables
50 mm or more
!
WARNING
30 mA max. (at 24 V DC)
Rush current: 10 A or less
φ
5.5 MAX
φ
3.2 MIN
φ
3.2
2
9.0 mm
5.6 mm
Power supply
terminals
Supply the power to only one of the
joined modules.
1
2
When power is supplied to any one of the
5
joined modules, all of the joined modules
+
will receive power.
24 V DC
Terminals 3, 4 and 5 (Usage is prohibited.)
(Continued on the next page
)

Advertisement

loading

Summary of Contents for Z-Com SRZ IMS01T05-E2

  • Page 1 COM. PORT2 The procedure for mounting or removing the Z-COM module is the same as that of the function away as possible from high voltage equipment, power lines, and rotating machinery. This instrument must be used in accordance with the specifications to Indication lamp (RX2/TX2) module (Z-TIO or Z-DIO).
  • Page 2 Host computer Z - C O M - A - codes to specify software configurable Customer is requested to prepare a communication cable fit for the Z-COM to be connected by the PLC. W-BF-02* settings. If not specified, these codes...

This manual is also suitable for:

Srz ims01t14-eSrz ims01t15-eSrz ims01t09-eSrz ims01t07-e