Philips FBP90 Specification

600 lumen linear fluorescent em. ballast

Advertisement

Quick Links

600 L
FBP90
9.4"
(23.9 cm)
2.4"
(6.1 cm)
1.5"
(3.8 cm)
L
UMEN
INEAR
Features
Illumination: The FBP90
provides 90 minutes of
emergency illumination by
utilizing existing fluorescent
lighting and produces 500-600
lumens initial emergency light
output. The FBP90 can be used
with most 17-40 W (2'-4')
T8, T10, or T12 fluorescent
lamps without integral starters,
including U-shaped, energy
saving, and 4-pin compacts. It is
also compatible with most 1-,
2-, 3-, and 4-lamp electronic,
standard, energy saving and
dimming AC ballasts. See lamp
operation for specific lamp
types.
Housing: Housing is
constructed of 20 gauge steel
with a high temperature
powder coat paint finish. Slim
housing allows for wireway
channel mounting on most
lighting fixtures.
Operating Temperature
Range:
32°F (0°C) to 131°F (55°C)
F
LUORESCENT
Electronics: 120/277 VAC
dual voltage input with surge
protected, solid-state charging
circuitry provides for a reliable
charging system. Charging
system is complete with AC
indicator lamp and test switch.
Electrical Specifications:
Input Power: 4 W max.
Battery
Maintenance free, sealed nickel
cadmium battery. Supplies 90
minutes of emergency power.
Estimated service life of 10
years.
Lamp Operation
1
: Operates
the following lamp types
2
:
T8 linear fluorescent (two lamp
operation)
T12 linear fluorescent
T9 circline
T12 U-bent
T5 long compact fluorescent
Notes:
1) Consult factory for compatibility,
operation and performance of product
with lamp types not listed.
2) See table 1 on back for specific lamp
performance and operation.
Job Information
Type:
Job Name:
Cat. No.:
Notes:
FBP90
E
. B
M
ALLAST
Page 1 of 2
Code Compliance
UL 924 and optional UL damp
location listed. NFPA 70, NFPA
101, NEC, BOCA, OSHA and
IBC illumination standards.
Suitable for use in sealed and
gasketed luminaires.
Warranty
One year full electronics
warranty. One year full battery
warranty.

Advertisement

loading

Summary of Contents for Philips FBP90

  • Page 1 FBP90 600 L UMEN INEAR LUORESCENT ALLAST Page 1 of 2 FBP90 Features Electronics: 120/277 VAC Code Compliance Illumination: The FBP90 dual voltage input with surge UL 924 and optional UL damp provides 90 minutes of protected, solid-state charging location listed. NFPA 70, NFPA emergency illumination by circuitry provides for a reliable 101, NEC, BOCA, OSHA and...
  • Page 2 2) Maximum emergency lumen output is based on total output of one or two lamps, and can vary based on lamp manufacturer and ambient operating temperature. 3) Consult factory for compatibility, operation and performance of lamp types not listed. Philips Lightolier Job Information Type: e: lol.webmaster@philips.com...

This manual is also suitable for:

Lightolier fbp90