REMOTE STATUS ALARM PANEL
RSAP
INSTALLATION/INSTRUCTION MANUAL
W3-002-SLSUPS-002A

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric REMOTE STATUS ALARM PANEL

  • Page 1 Mitsubishi Electric Automation, Inc. UPS Group REMOTE STATUS ALARM PANEL RSAP INSTALLATION/INSTRUCTION MANUAL W3-002-SLSUPS-002A...
  • Page 2: Table Of Contents

    Table of Contents Physical Characteristics..............2 Installation instructions..............2 Operating instructions................ 3 Remote Monitor Closed (Figure 1.0)…..........4 Remote Monitor Closed Hardwired (Figure 1.1)....... 5 Terminal Block Description (Figure 2.0)........... 6 Terminal Block Description Hardwired (Figure 2.1)......7 Remote Monitor Open (Figure 3.0)…..........8 Remote Monitor Open Hardwired (Figure 3.1)........
  • Page 3: Physical Characteristics

    Physical Characteristics Weight: 10lbs (4.5 kgs.) Height: 81/4 inches (210 mm) Width: 8 5/16 inches (211 mm) Depth: 4 5/16 inches (110 mm) Installation 1. Locate the area where the Remote Status Alarm Panel (RSAP) will be installed. The monitor should be within 300 feet (91 meters) of the UPS. 2.
  • Page 4: Operating Instructions

    3. If the monitor's audible alarm sounds again repeat steps 1and 2. 4. Contact Mitsubishi service if the alarm cannot be reset after a few attempts. Refer to Figure 1.0 for the location of the LED's and pushbuttons described below: 1.
  • Page 5: Remote Monitor Closed (Figure 1.0)

    10/13/04 93120-MAN07...
  • Page 6: Remote Monitor Closed Hardwired (Figure 1.1)

    10/13/04 93120-MAN07...
  • Page 7: Terminal Block Description (Figure 2.0)

    -AC INPUT L1 (OPTION) -AC INPUT L1 (OPTION) -BYPASS (CLOSES WHEN ON BYPASS) -BYPASS COMMON -INVERTER (CLOSES WHEN INVERTER IS RUNNING) -INVERTER COMMON -ON BATTERIES (CLOSES WHEN ON BATTERIES) -BATTERY COMMON -RECTIFIER (CLOSES WHEN RECTIFIER IS RUNNING) -RECTIFIER COMMON -UPS FAILURE (CLOSES ON UPS FAILURE) -UPS COMMON -LOW BATTERY (CLOSES WHEN BATTERIES ARE LOW) -LOW BATTERY COMMON...
  • Page 8: Terminal Block Description Hardwired (Figure 2.1)

    -AC LINE INPUT L1 -AC NEUTRAL INPUT -GROUND -NOT USED -BYPASS -BYPASS COMMON -INVERTER (CLOSES WHEN INVERTER IS RUNNING) -INVERTER COMMON -ON BATTERIES (CLOSES WHEN ON BATTERIES) -BATTERY COMMON -RECTIFIER (CLOSES WHEN RECTIFIER IS RUNNING) -RECTIFIER COMMON -UPS FAILURE (CLOSES ON UPS FAILURE) -UPS COMMON -LOW BATTERY (CLOSES WHEN BATTERIES ARE LOW) -LOW BATTERY COMMON...
  • Page 9: Remote Monitor Open (Figure 3.0)

    10/13/04 93120-MAN07...
  • Page 10: Remote Monitor Open Hardwired (Figure 3.1)

    10/13/04 93120-MAN07...
  • Page 11: Remote Monitor Conduit Access (Figure 4)

    10/13/04 93120-MAN07...
  • Page 12 Load on Bypass Load on Bypass Selectable Item 1 16 awg twisted pair recommended Note: TB1 terminals 6 and 16 not shown for clarity. Terminals are connected internally. Mitsubishi Electric Remote Status Alarm Panel Automation, Inc. (RSAP) Interconnect Diagram 02-15-00 Date...
  • Page 13 Common Load on Bypass Load on Bypass 14 awg shielded wire recommended Note: TB1 terminals 6 and 16 not shown for clarity. Terminals are connected internally. Mitsubishi Electric Remote Status Alarm Panel Automation, Inc. (RSAP) Interconnect Diagram 03-10-98 Date Page...
  • Page 14 Load on Inverter Load on Bypass Load on Bypass Common Common Load on Bypass Load on Bypass 16 awg twisted pair recommended Mitsubishi Electric Remote Status Alarm Panel Automation, Inc. (RSAP) Interconnect Diagram 02-15-00 Date Tom Kobayashi Page Drawn by...
  • Page 15 Common Load on Inverter Inverter Load on Bypass Bypass Common Common Load on Bypass Bypass 14 AWG shielded wire recommended Mitsubishi Electric Rev A Remote Status Alarm Panel Automation, Inc. (RSAP) Interconnect Diagram 8/29/03 Date Carl E. Luecht Page Drawn by 2033D/9800AD DWG No.
  • Page 16 Common Load on Bypass Load on Bypass 14 awg shielded wire recommended Note: TB1 terminals 6 and 16 not shown for clarity. Terminals are connected internally. Mitsubishi Electric Remote Status Alarm Panel Automation, Inc. (RSAP) Interconnect Diagram 10-21-97 Date Page...
  • Page 17 Load on Inverter Load on Inverter Load on Bypass Load on Bypass Common Common Load on Bypass Load on Bypass 14 awg shielded wire recommended Mitsubishi Electric Remote Status Alarm Panel Automation, Inc. (RSAP) Interconnect Diagram 07-09-99 Date Page Mario Recine...