GEH6503 Installation Instructions
Power Break II Circuit Breakers in NEMA 1 Enclosures
800,1600, and 2000 Amperes
Introduction
These instructions describe the installation of 800, I 600,
and 2000 ampere frame-size Power Break® II insulated-
case circuit breakers in NEMA I enclosures, illustrated in
Figure I. Table I lists the catalog numbers of the enclo-
sures and the corresponding field-installed neutrals for
the carious breaker frame sizes.
Enclosure Catalog
Number
SPB08W
SPB16W
SPB20W
Table 1. Catalog numbers of enclosures and field-installed
neutrals for Power Break II circuit breakers.
Conduit Openings
1. Conduit openings in the top and/ or bottom
end walls should be completed before the
enclosure is mounted to the wall.
2. It may· be easier to remove the enclosure end
walls to make the conduit openings. Remove
the door hinge screws and then detach the
door.
3. Remove either the top or bottom end wall, but
not both, since side wall stability would be
greatly reduced. Make the conduit openings in
the removed end wall. Replace the end wall.
Ensure that all mounting screws are replaced
and tight­ened to 4 0-50 lb-in torque.
4 . If required, remove the other end wall, make
the conduit openings, and replace the end wall,
as in step 3.
5. For easier cable and device installation, do not
reattach the door until installation is complete.
Circuit Breaker
Envelope Size
Catalog Number
800 A
1600 A
2000 A
Neutral
TNT800
TNT1600
TNT2000
Figure 1. 2000 ampere enclosure, catalog number SPB20W.

Advertisement

loading

Summary of Contents for ABB SPB08W

  • Page 1 Figure I. Table I lists the catalog numbers of the enclo- sures and the corresponding field-installed neutrals for the carious breaker frame sizes. Circuit Breaker Envelope Size Enclosure Catalog Neutral Number Catalog Number SPB08W 800 A TNT800 SPB16W 1600 A TNT1600 SPB20W 2000 A TNT2000 Table 1.
  • Page 2 4.Tighten all terminal bolts and nuts to 300-400 lb­in Dimensions (in) Weight (2 5 -33 lb-ft) torque. Catalog No. (lb) 51.5 29.5 SPB08W 14.5 53.5 SPB1�W SPB20W Table 2. Enclosure dimensions and weight --- 2 8.99------t �: �.62 i---- -- 29.50 (W)
  • Page 3 1.- - - - 3 8.4 9 0.25 Lifting Plates 14.25 2.00 • 0.81 r-1 3 .75-->j Detail A Typical 88.00 • 86.00 89.50 • 38.92 2.00 Rgure 3. Dimensions of 1600-2000 A Enclosures. Final Installation Checks 1. Check all cable-to-lug connections. Tighten each lug screw to the torque range specified in Table 3 for the Dimension Torque...
  • Page 4 – in whole or in regard to purchase orders, the agreed parts – is forbidden without prior written particulars shall prevail. ABB Inc. does not accept any responsibility whatsoever for consent of ABB Inc. Copyright© 2019 ABB...

This manual is also suitable for:

Spb16wSpb20wTnt800Tnt1600Tnt2000