Download Print this page

olympia electronics MLD-28S/g Manual

Maintained/non maintained illumination signs with green leds

Advertisement

Quick Links

MAINTAINED/NON MAINTAINED ILLUMINATION SIGNS WITH GREEN LEDs
TECHNICAL CHARACTERISTICS
Mains voltage
Maximum power consumption
Battery (Ni-Cd)
Battery protection
Recharging time
Minimum emergency duration
Light source intensity (Mains / Emerg)
Degrees of cover protection
Class of cover protection
Produced in accordance with
Operation temperature range
Relative humidity
External panel's dimensions
External dimensions (LxWxH)
Construction materials
Typical weight
Guarantee
GENERAL
These new sign illumination luminaires, use a new
technology, friendly to the environment , with high
illuminated
L.E.D.s. L.E.D. technology has very low
power consumption. The edge illumination sign is used
as a maintained backup lighting with indications
symbols. Each package contains arrows stickers which
are used to quickly design the required sign which is
suitable for each occasion.
Just place the sign on the figure which is designed on
the packages and stick the arrow.
Each model combines modern, aesthetics, together
with functionality. The exit illumination signs are used in
every public area where clear direction and good
appearance are important.
NON MAINTAINED OPERATION
By default the illumination sign operates as maintained.
The device has a possibility to operate as non
maintained. To change the maintained to non
maintained operation follow the relative instructions on
page 6. All models must be permanently connected to
the mains power supply as shown on page 2. The
legend is screened on to a clear acrylic sheet which
has the marking on the marking panel with the light that
comes from the top of the luminaire and diffracts, giving
light to the marking panel. The luminaire has an
indication (CHARGE) for the charging of the battery
and a (TEST) button to TEST the emergency circuit
and the LEDs for good operation only when the
luminaire is powered by the mains power supply. The
unit must be mounted in a clearly visible area and can
either be hung on a ceiling or mounted on a wall
Page 1 from 6
MLD-28S/g
3W / 7.5VA
18lm / 18lm
EN 60598-1, EN 60598-2-1, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
280x100mm
305x25x155mm
Thank you for your trust in our product
Olympia Electronics - European manufacturer
(for LED MODULE Specs. see page 4)
MLD-34S/g
220-240V AC/50-60Hz
3.6V/1Ah
Overcharging and deep discharging protection
class II
5 to 40 C
Up to 95%
340x170mm
350x25x205mm
ABS/PC,Plexiglass,PVC
500gr.
3 years (1 year for the battery)
depending on the requirements of the installation.
The package includes all the required materials for
mounting on the wall or on the ceiling. The pages
2,3 and 4 show us the mounting methods.
WARNING !!
1. Read carefully this instruction manual.
2. Before service interrupt the mains power supply.
3. The device must be connected to the mains
power supply through a fuse dependent by the total
amount of the line's power load.
4. It is suggested to check every month the
indication LED for battery charging, and by pushing
briefly the TEST button to check the emergency
circuit. The sign should light for a few seconds
powered by the battery and then, will turn to normal
operation. In the opposite condition contact the
installer.
5.
Every six months, a
carried out
by disconnecting the mains power
supply Count the autonomous duration of the
.
luminaire and in case of no correspondence to
stated emergency duration replace the battery The
replacement of the battery must be done using parts
of the same type, by the manufacturer or by a
competent person.
6. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery's connector.
7 Replaced batteries must not be thrown into
.
trash bins. They must be returned to
special battery disposal points. Do not
incinerate.
MLD-44S/g
3W / 8VA
24h
3h
22lm / 18lm
IP 40
ο
440x220mm
465x25x275mm
1160gr.
800gr.
full
duration check should be
922504400_09_027
.

Advertisement

loading

Summary of Contents for olympia electronics MLD-28S/g

  • Page 1 800gr. 3 years (1 year for the battery) Guarantee Thank you for your trust in our product Olympia Electronics - European manufacturer GENERAL depending on the requirements of the installation. These new sign illumination luminaires, use a new The package includes all the required materials for technology, friendly to the environment , with high mounting on the wall or on the ceiling.
  • Page 2: Mounting Methods

    MOUNTING METHODS Preparation procedure Connection of the included terminal block for ceiling mounting BROWN 230V AC BLUE Attention!!! Interrupt the mains power supply. Hanging installation on suspended ceilings using the special mounting brackets 1. Open the pre-etched knock out and pass the cable through.
  • Page 3 Ceiling Mounting MLD-28 S: 22cm MLD-34 S: 28cm MLD-44 S: 37,5cm 5. Place the mounting accessories in the wall and tighten the mounting screw. 1. Place the plastic mounting part 2. Tighten the screw. 3. Pass the cable in the canal. 4.
  • Page 4: Wall Mounting

    3. Plastic bag with supporting MLD-28 : 305(a) x 95(b) materials. MLD-34 : 365(a) x 165(b) MLD-44 : 465(a) x 215(b) LED MODULE CHARACTERISTICS MLD-28S/g MLD-34S/g MLD-44S/g Olympia Electronics S.A. Manufacturer Model Number 1702161 1802161 1902161 Voltage Range 12-14V DC Nominal Power...
  • Page 5 BATTERY REPLACEMENT PROCESS Before service interrupt the mains power supply. 1 Remove the plastic cover from each side. (figure 1, step 4). 2 Unfasten the mounting screws to unmount the illumination sign (figure 1, step 2). 3 You have to disconnect the power supply wires of the sign from the terminal block. 4 Unfasten the mounting screw of the bracket and remove it.
  • Page 6: Troubleshooting

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Mld-34s/gMld-44s/g