  • Page 1 www.ic-electronic.com...
  • Page 2 Automatic reset after failure. Selection and technical specifications. Product type Rated operational EAN Nr. Rated operational Control voltage Ue current Ie voltage Uc SCL 33 DA 4015BP 400VAC 5705609002893 15A AC 58b 230VAC SCL 33 DA 4025BP 400VAC 5705609002909 25A AC 58b 230VAC...
  • Page 3 Costumer Advantage: Current reduction up to 65% peak, extend mechanical lifetime of the compressor. Current reduction eliminates the voltage clips and light flickering. Real RMS current measurement, for exact control of the current. Mounting from the top and down. Spring clamps for fast and easy mounting. Internal motor protection (I t- metering, using class 10 trip curve) gives reduction in cost for external motor protec- tion and wiring.
  • Page 4: Technical Specifications

    LRA max. 66/100/140 A; automatic adjusted @ motor. Semiconductor data Product type Rated operational current Short circuit protection SCL 33 DA 4015BP 610 A max.: 35A gl/gG SCL 33 DA 4025BP 1800 A max.: 63A gl/gG SCL 33 DA 4035BP 1800 A max.: 63A gl/gG...
  • Page 5 Fault: Environent: LED red (alarm signals via user friendly flashing sequence) High voltage / low voltage / Voltage Degree of protection : IP 20 High current / low current Pollution degree Current not symmetrical Operating temperature : -200 to 650C Motor protection (I Storage temperature : -200 to 800C...
  • Page 6: Normal Conditions

    Motor Protection: The internal electronic motorprotection is automatically temperature compensated. The motor protections acts exactly as an external motor protection circuit breaker. < Cold Figure: Electronic Motorprotection Class 10. Mode of Operation: Normal Conditions Main Voltage Yellow LED 5 min. Ctrl.
  • Page 7 Locked Rotor/Fault (4) Main Voltage Yellow LED Ctrl. Volt Motor Signal Alarm Alarm Out < > 3 min. < > 5 min. Break High Temperature/Fault (6) Main Voltage Yellow LED Ctrl. Volt Motor Signal Alarm Alarm Out < Condition fultilled >...
  • Page 8 Standards Restrictions of hazardous substances RoHs Compliant CE Marking EN 60947-4-2 EMC: Immunity EN 61000-6-4 Emission EN 61000-6-2 Electrostatic Dicharge ESD Immunity EN 61000-4-2 8kV, Air discharge 4kV, Contact Electrical fast transient/ Burst Immunity EN 61000-4-4 Output Input Electrical Surge Immunity EN 61000-4-5 Output, line to line Output, line to earth...

This manual is also suitable for: