Synchro-check Monitor PLL/D-100/120, PLL/D-173/240,
PLL/D-380/480, PLL/D-277/500 DIN-rail mounted
Introduction
This unit compares the voltage, frequency and phase angle of two
supplies and operates a relay according to the synchronicity of the
supplies. If the two supplies cease to match, the relay operates to
provide a control output. The relay output can be used for alarm or
control purposes.
The unit also provides a dead bus function. If the bus supply fails, the
relay operates and the output can be used to switch in an emergency
generator. LEDs indicate power on, relay and dead bus status.
Controls on the front panel set the trip points at which the relays and
LEDs operate:
Degree of synchronicity Ux (%Volts)
Nominal voltage (Un)
Dead bus function on/off
The unit is powered from the generator supply.
These instructions contain important safety information. Please read
them thoroughly before commissioning, operating or maintenance of
the unit.
Specification
Parameter
PLL/PLD
Rated Vg range Un
Overload capacity
- continuous
- 10s max.
Minimum supply Vg Uon
Burden on supply (Max)
Frequency range
Deadbus on Udbon
Deadbus off Udboff
Sync Tolerance
Relay contacts: for
general switching
Load capacity - a.c.
Load capacity - d.c.
Insulation
Mech. endurance
Other Data:
Dimensions
Weight
(100/208/380/277)
Maximum conductor
size
Operating temperature
Storage temperature
Over-voltage category
Pollution degree
Environmental
protection
Standards
Insulation Class: Ensure any external circuits connected to the
relay are provided with double or reinforced insulation.
Operation
The green
LED lights shows when the power supply is on.
While the two supplies match in voltage, frequency and phase to the
degree set by the %Volts control, the Sync LED lights and the relay is
energised.
If one supply varies such that they no longer match to that degree, the
Sync LED goes off and the relay de-energises.
Ref: PLL/D APR11-REV1
100/120
173/240
380/480
57-69V
100-
220-
139V
277V
87V
174V
346V
104V
209V
416V
35V
60V
132V
2 VA /
2.7 VA /
4 VA /
1.6W
1.7W
2.2W
45-65 Hz
25% Uon
50% Uon
10-30% Volts
2 x changeover, volt-free
250V @ 8A, 2 kVA
30V 8A
4 kV/1 min
6
30x10
operations
90 x 105 x 64 mm
291 / 335 / 332 / 335 g
2
2 x 1.5 mm
or 1 x 2.5 mm
-20 to +55 °C
-30 to +70 °C
III
2
IP40 for front panel
IP20 for terminals.
EN 60255-6, EN 60255-27, EN 61000-6-2,
EN 61000-6-4
Installation and Operating
The differential trip levels help to prevent relay chatter as the
monitored voltage level varies.
277/500
As the relays have changeover contacts, the relay outputs can be
inverted by wiring to the alternative terminals 15-16 or 25-26.
277-
500V
If the generator voltage falls below the Uon level, the unit ceases to
600V
operate, the relay de-energises and the Sync LED goes off.
700V
With Dead Bus On, if the bus voltage falls below the Udbon level, the
166V
relay energises and the Dead Bus LED lights. The relay can be used
5 VA /
to turn on an emergency supply in the event of bus supply failure. The
2.8W
relay will de-energise again and the LED will go off when the bus
voltage rises above the Udboff level.
Note; Red LED indicates fault condition, not relay status
Installation
The unit is intended for mounting on a standard DIN rail. Hook the unit
onto the top of the rail and press the bottom of the unit until it locks in
place. To remove the unit from the rail, lever down the black tabs at
the bottom of the unit to release it from the rail.
The unit is intended for use in a reasonably stable ambient
temperature within the range -20 to +55°C. Do not mount the unit
where there is excessive vibration or in excessive direct sunlight.
2
Page 1 of 2
Instructions

Advertisement

loading

Summary of Contents for TE Connectivity PLL/D-100/120

  • Page 1 Installation and Operating Instructions Synchro-check Monitor PLL/D-100/120, PLL/D-173/240, PLL/D-380/480, PLL/D-277/500 DIN-rail mounted Introduction This unit compares the voltage, frequency and phase angle of two supplies and operates a relay according to the synchronicity of the supplies. If the two supplies cease to match, the relay operates to provide a control output.
  • Page 2 Our liability for these products is set forth in our standard terms and conditions of sale. TE connectivity (logo), TE (logo) and TE Connectivity are trademarks of the TE Connectivity Ltd. family of companies. CROMPTON is a trademark of Crompton Parkinson Ltd.
  • Page 3 Operating Instructions Fusing A suitable switch or circuit breaker conforming to the relevant parts of IEC Synchro-check Monitor PLL/D-100/120-UL, 60947-1 and IEC 60947-3 should be included in the building installation. PLL/D-173/240-UL, PLL/D-380/480-UL, It should be positioned so as to be easy to operate, in close proximity to the equipment, and clearly identified as the disconnecting device.
  • Page 4 Maximum conductor 2 x 1.5 mm or 1 x 2.5 mm (12AWG) size Surrounding air -20 to +55 °C temperature rating Storage temperature -30 to +70 °C Over-voltage category Pollution degree Environmental IP40 for front panel protection IP20 for terminals. (Not evaluated by UL) Standards EN 60255-6, EN 60255-27, EN 61000-6-2,...