Electropneumatic Transducer (I/P) Nitra NCP1 Installation, Operation and Series Maintenance Instructions Ordering Information Contents NCP1 Series I/P Transducers Section Description Page Output Range Part Number Input Description & Installation psig Operation NCP1-20-315N 4-20 mA 3-15 0.2-1.0 NCP1-20-327N 4-20 mA 3-27 0.2-1.9...
Page 2
1. DESCRIPTION and INSTALLATION 1.1 Description 1.1.1 The NITRA NCP1 Series converts a current input signal to a linearly proportional pneumatic output pressure. This versatile instrument is designed for control applications that require a high degree of reliability and repeatability at an economical cost.
Page 3
1.2 Principle of Operation 1.2.1 The NITRA NCP1 Series is a force balance device in which a coil is suspended in the field of a magnet by a flexure. Current flowing through the coil generates axial movement of the coil and flexure. The flexure moves towards the nozzle and creates back pressure which acts as a pilot pressure to an integral booster relay.
Page 4
7. The Zero and Span adjustments are interactive. After adjusting the span it will be necessary to recheck the zero. Repeat steps 3-6 until both end points are at the required values. 2.2 Dimensional Drawings (Dimensions are inches [mm]) NCP1 Series Page 4...
Page 5
(large silver screw head located above the out port). Then unplug orifice by using a wire that has a smaller diamter than 0.015 in. (0.38 mm). Use compressed air to blow out any loose particles inside the orifice assembly. Screw orifice assembly back into unit. NCP1 Series Page 5...
Page 6
See AutomationDirect.com for latest Terms & Conditions These products are intended for use in industrial compressed-air systems only. Do not use these products where WARNING pressures and temperatures can exceed those listed under Specifications. Not for oxygen service. NCP1 Series Page 6...