The 4 -20mA re-transmitted signal is optically isolated from the input signal. By default the re-transmittion parameters are set so that the
output follows the full scale input.
Description:
This device is used to display and monitor DC voltage. Maximum & Minimum values are logged for 24 hours (updated every 60 min).
The relay(s) may be used for over and / or under protection. The latch facility may be de-activated for one or both the relays
allowing one relay to be used for control (not latched), and the other as a latched alarm. Use the "ScAL" parameter for calibration
purposes, or to change the number of decimal places displayed (see notes). Other features include adjust able signal damping,
adjustable start-up and reaction delays, the ability to swap the relay's functionality. All settings may be locked & code protected
to avoid changes from being made by unauthorised personnel.
0 RELAY
This device is used to display DC voltage.
1 RELAY
The voltage applied is displayed according to the scale specified. The relay remains energised while the input signal is between
the upper and lower set points. Once de-energised, the signal must change in the opposite direction by the hysteresis amount
before the relay will re-energise. The relay's action may be swapped to energise when the setpoint is reached. Note: the relay
will NOT re-energise while the latch pins are shorted. The latch pins can also be used as a reset.
2 RELAY
The voltage applied is displayed according to the scale specified. The relays remain energised while the input signal is between
the upper and lower set points. Once de-energised, the signal must change in the opposite direction by the hysteresis amount
before the relay will re-energise. Either relay's action may be swapped to energise when the setpoint is reached. Note: the
relay will NOT re-energise while the latch pins are shorted. The latch pins can also be used as a reset.
Adjustable parameters:
Please note: Depending on the model of the device purchased, some of the parameters listed below may not be available
· Upper limit for relay 1 "Hi 1" (default: disabled)
When the input rises above this value, the relay changes state until the signal drops by the hysteresis amount
(see "HYS.1" setting)
· Lower limit for relay 1 "Lo 1" (default: disabled)
When the input drops below this value, the relay changes state until the signal rises by the hysteresis amount
(see "HYS.1" setting)
D3
53mm
DIN rail mount
DC VOLTAGE MONITOR
incl 4-20mA or 0-10V re-transmit
EXAMPLE: D3-MD 0-T = 0 RELAY
Operating instructions and Guarantee Certificate
www.iconelectronics.co.za
P44
48mmx48mm
panel mount
D3-VMD 0/1/2-T
P44-VMD 0/1/2-T
P49-VMD 0/1/2-T
P49
48mmx96mm
panel mount

Advertisement

loading

Summary of Contents for Icon Electronics D3-VMD0-T

  • Page 1 48mmx96mm 53mm 48mmx48mm panel mount DIN rail mount panel mount DC VOLTAGE MONITOR incl 4-20mA or 0-10V re-transmit D3-VMD 0/1/2-T P44-VMD 0/1/2-T P49-VMD 0/1/2-T EXAMPLE: D3-MD 0-T = 0 RELAY Operating instructions and Guarantee Certificate www.iconelectronics.co.za ReTransmit devices (-T) The 4 -20mA re-transmitted signal is optically isolated from the input signal. By default the re-transmittion parameters are set so that the output follows the full scale input.
  • Page 2 · Hysteresis value for relay 1 “HYS.1 “ (default: 0.5 ) Once the set-point is reached, (& relay changed state), the input signal must change (in the opposite direction) by this value before the relay will return to its original state. ·...
  • Page 3: Specifications

    · Re-transmit output SPan “rt.SP’ (default value: programmed display span value) When the display indicates this value PLUS the offset value (“rt.SP’+”rt.OS”), 20mA is transmitted. (see notes). · Reset “RESt” By selecting this setting, the device is reset to the factory defaults press “ ”& “ ” or “+” & “-” together to select. DUAL DISPLAY DEVICE PROGRAMMING Example 1: Set the device to de-energise relay 1 when the voltage is below 10.0V and above 90.0V If all of the following settings are NOT available, exit the menu and activate the advanced menu.
  • Page 4 re-transmit Notes: · The output 4-20mA is dependant on the value being displayed, and is set up in a similar manner to the display. The offset parameter determines when 4mA is output, and the span is the amount required for the output to increase by an additional 12mA ie.