SCC-T1-Tp2 Temperature transmitter for PT1000 probes
Features
•
Precision temperature measurement for different ranges and
accuracies
•
Minimum and maximum value memory
•
0...10V, 0...20mA or 2...10V, 4...20mA measuring signals,
selectable with jumpers
•
Optional alternative signal ranges programmable
Selectable averaging signal
•
Optional LCD display (OPC-S) or external display (OPU-S)
•
Status LED
•
Applications
•
For indoor, outdoor, duct, immersion temperature
measurement for heating, ventilation and air conditioning
applications
•
Recording of minimum and maximum values for critical environments
•
Supervision of critical temperatures
Temperature transmitter
The transmitter measures the temperature for a PT1000 platinum film element. The transmitter does not include the
PT1000 sensor. An external PT1000 according to EN 60751 has to be connected for the transmitter to operate.
The microprocessor samples the temperature once per second. It calculates an averaging signal over a preset number of
seconds and generates an output signal based on lower and upper signal range values. Standard range is
-40...400°C (-40...752°F) and 1 second's average.
The output signal range and type may be customized by jumpers and if required by a programming tool. Standard signal
ranges are 0-10VDC, 2-10VDC, 4-20mA and 0-20mA. These ranges can be set by jumpers. Other ranges can be set on the
–OP transmitter or by connecting OPU-S.
Minimum and maximum values
By using a display module (-OP or OPU-S), the user has the option to read out and reset minimum and maximum values.
The minimum and maximum values may as well be used as output signals. The minimum and maximum values are saved
into a non-volatile memory and are therefore available after a power interruption.
Types and Ordering
Part Name
Part No.
SCC-T1-Tp2
40-300075
SCC-T1-Tp2-OP
40-300076
Accessories
Part Name
Part No.
S-Tp2-2
40-200012
SD-Tp2-12-2
40-200024
SD-Tp2-20-2
40-200027
SDB-Tp2-12
40-200056
SDB-Tp2-20
40-200034
SRA-Tp2
40-200041
SOD-Tp2
40-200064
OPU-S
40-500030
AMC-1
20-100035
AMC-2
20-100067
Doc: 70-07-0175B, V1.0, 20210326
Subjects to alteration
Measuring Temperature Range
-40...400°C (-40...752°F)
-40...400°C (-40...752°F)
Description
Flying lead sensor, 2 m cable
Flying lead duct sensor; Probe length 12 cm, 2 m cable
Flying lead duct sensor; Probe length = 20 cm, 2 m cable
Duct sensor, Probe length 12 cm
Duct sensor, Probe length 20 cm
Indoor sensor
Outdoor sensor
External display module
Cable gland PG9 for cables 4 – 8 mm (AWG 6 – 1)
Conduit connector NPT 1/2
© Vector Controls LLC, USA
www.vectorcontrols.com
SCC-T1-Tp2(-OP) for PT1000 probes
Options
Includes display module OPC-S
Product Data Sheet
Page 1-6