Designed specifically for new construction, "bid spec" market place, the CSM series
of surge protective devices provides the features, performance and value required
by discriminating specifying engineers. This device is intended for protection of
critical and sensitive load applications ranging from individual equipment
disconnects, sub panels and distribution panels to service entrances. It is extremely
effective in limiting lightning surges as well as internally generated transients.
The CSM series provides an effective blend of leading edge suppression design
technology, straight forward, no frills engineering and customer driven, value added
options. Specify the CSM with confidence.
Description:
Parallel connected, AC power Surge Protective Device.
Application:
Designed for use at ANSI/IEEE C62.41.1 & C62.41.2 location
categories C, B and A. Designed to protect critical and sensitive
loads fed from individual disconnects, sub panels, distribution
panels and service entrance locations.
Warranty:
15 Years
Unit Listings:
Listed to ANSI/UL 1449 4
(MC#241804); UL1283
Circuit Design:
Parallel connected, multi-stage hybrid Frequency Responsive
Circuitry circuit design incorporating discrete all mode protection
and both component level thermal fusing and internal over-current
fusing. All protection circuits are encapsulated in our high-dielectric
compound to promote long component life and protection from the
weather and vibration.
Protection Modes:
All Mode - L-L, Discrete L-N (Normal Mode), and Discrete L-G,
N-G (Common Mode).
Input Frequency:
50-60 Hz (60 Hz typical)
Frequency:
Insertion Loss Data:
Attenuation:
(L-N for 3Y1)
Circuit Diagnostics:
LED, 1 per phase, normally on. See pg. 2 for additional
diagnostics options
Connection/mounting:
#10 Wire (pre-installed), hub (pre-installed on base models,
installed at time of installation on optional enclosures) and integral,
multi-point mounting feet.
Circuit Interrupt:
Internal component-level, thermal fusing and patented circuit board
mounted, over-current fusing. No external over-current protection
required. (Note: National and local codes may require the use of a
circuit interrupt device(s) if conduit is added to make the wired
connection to the panel or gear.) SCCR = 200 kA
Nominal Discharge
10 kA (CSMA6);20 kA (CSMB6**) (
Current (I
) Rating:
UL 96A Master Label for Installation Requirements for Lightning Protection
n
Systems
Voltage
Code
L-N
1P1
600
1S1
600
3Y1
600
3D1
600
3Y2
1200
3N4
-
PO Box 15732, Brooksville, FL 34604 - Phone: 888-987-8877/850-654-5559, Fax 850-654-3844
th
Edition by UL (E315947), CSA
10 kHz
100 kHz
14 dB
38 dB
)
ANSI/UL 1449 (Fourth Edition)
Voltage Protection Rating (VPR)
HL-N
L-G
HL-G
-
600
-
-
600
-
-
600
-
1200
600
1200
-
1200
-
1200
-
1800
-
www.surgesuppression.com
2018 SSI
1 MHz
Max Attenuation & Freq.
21 dB
52 dB @ 148 kHz
**
Complies with the requirements of
N-G
L-L
HL-L
700
-
-
700
1200
-
700
1200
-
700
1200
1800
2500
-
-
1800
-
®
. Rev Date 10/4/2018
Page 1 of 2
SS05966
CSMx6 Series
60 kA Per Phase
Peak Surge Current
ANSI/UL1449 UL Fourth Edition
A = Type 2 SPD, I
= 10 kA
n
B = Type 2 SPD, I
= 20 kA
n
Key Features:
Industry Leading Measured
Limiting Voltage Performance
EMI/RFI Parallel Configured
Listed to UL 1283
Independent Verification of
Performance and Safety
Component-Level, Thermal
Fusing and Over-Current Fusing
No moving parts or springs - No
mechanical or electro-mechanical
thermal/over-current protection
Circuit Encapsulation