Inbal Deluge Valve, Hydraulic Actuation
Series 700D/DG/DX - 04/24A01
F M
A p p r o v e d
General Description
The Inbal Deluge Valve with Hydraulic Actuation Trim is
specifically designed for fire protection systems actuated by
a fire detection and release system of wet pilot sprinklers
and/or hydraulic manual control. The Inbal Automatic Water
Control Valve, which is used in this deluge system, is a
pressure operated, sleeve actuated, axial valve designed
for use in fire protection systems.
The Inbal Hydraulically actuated Deluge Valve is used for
automatic or manual operation. The wet pilot line functions
as a thermal detector equipped with a fixed temperature
release. When one or more of the sprinkler heads, located
on the pilot line, fuses, or when a manual release station is
operated locally or remotely, the Inbal Deluge Valve opens
and water flows from all open sprinklers and/or nozzles on
the system. As soon as the releasing system and the
sprinkler piping are reset, the Inbal Deluge Valve resetting is
merely done by activating the reset knob.
Page 1/6
Local Resetting
The control trim includes all the pilot valves, accessories,
fittings, and gauges to provide for proper operation in either
vertical or horizontal installation. The standard material
Inbal Deluge Valve is rated to 300 psi (21 bar) and is
available in sizes 1½" (40 mm) to 12" (300 mm). The valves
have threaded, flanged, grooved, or wafer inlet and outlet
ends.
The only moving part in the Inbal Deluge Valve, when it
operates, is the reinforced sleeve, which forms a drip-tight
seal with the corrosion resistant core. It has a smooth
opening to prevent any water hammer in the piping system.
The unique design and variety of materials and coatings
make the Inbal Deluge Valve ideally suitable for use in
brackish or sea water, similar to those found in chemical and
petrochemical facilities or in offshore platforms. The Inbal
can also be used as a foam concentrate control valve in
foam/water systems.
F03-02-04-001
®
Model 799DG-04A01

Advertisement

loading

Summary of Contents for Inbal Valves 700D Series

  • Page 1 ® Inbal Deluge Valve, Hydraulic Actuation Series 700D/DG/DX - 04/24A01 Local Resetting A p p r o v e d Model 799DG-04A01 General Description The Inbal Deluge Valve with Hydraulic Actuation Trim is The control trim includes all the pilot valves, accessories, specifically designed for fire protection systems actuated by fittings, and gauges to provide for proper operation in either a fire detection and release system of wet pilot sprinklers...
  • Page 2: Technical Data

    Technical Data Approvals AS 2129 Table D & E; The Inbal Hydraulically Controlled Deluge Valve models: Jis B 2212, 2213, 2214. 711D -24A01 733D -24A01 799D -24A01 Grooved End: 711DX -24A01 733DX -24A01 799DX -24A01 ANSI/AWWA C606-87. 711DX -04A01 733DX -04A01 799DX -04A01 Wafer End: 711DG-24A01...
  • Page 3 Schematic Control Diagram 700DG-04A01 1 Inbal Automatic Water Control Valve To Deluge System 2 Emergency Release Station 3a Test Valve Inspector's 3b Trim Shutoff Valve Test Valve 4 Y-Strainer 5 Flow Release Pilot (F.R.P.) 18 Automatic Drain Valves DRAIN 21a Supply Pressure Gauge 21b System Pressure Gauge 29 Alarm Test Valve DRAIN...
  • Page 4: Operation

    Wet Pilot Line - Design Data m H O ft H O WATER SUPPLY SYSTEM PRESSURE Based on ½'' (15 mm) Schedule 40 pipe If the maximum elevation of hydraulic release piping exceeds the limits shown on the graph, use anticolumning device model 395-08 (see bulletin F40-14-01). Graph (1) Wide range of sizes for an ideal system design.
  • Page 5: Installation

    Installation Resetting Refer to the Trim Chart applicable to the specific Inbal The Inbal Deluge Valve system must be reset and restored Deluge Valve model in use. to service as soon as possible after automatic, emergency, 1. When the Inbal Deluge Valve is delivered, carefully or manual actuation.
  • Page 6 Copyright by Mil Inbal Valves Ltd. All rights reserved© Inbal Valves® is a registered trademark The information contained in this document is subject to change without notice. Mil Inbal Valves Ltd shall not be liable for any errors, omissions or amendments contained herein Page 6/6...

This manual is also suitable for: