Shipping & Packing List
Package 1 of 1 contains:
1 − Danfoss RTC DDC assembly (A1)
1 − Return air sensor (A2) with P62 connector
1 − Discharge air sensor (RT1) with P63 connector
1 − Bracket, DDC controls
1 − Bag assembly containing:
4 − #8−32 X 1/2" screws
1 − Wiring diagram sticker
6 − #10−16 X 5/8" screws
Application
The Danfoss RTC DDC is used with SCC/SGC series
units.
An A2 return air sensor monitors return air temperature
and provides input to the DDC to determine unit heating or
cooling function.
An A74 room air sensor is used to monitor space tempera-
ture. Do not install the return air sensor if a room air sensor
is used. The room air sensor is wired to the Prodigy® con-
trol by the controls contractor.
The RT1 discharge air sensor monitors discharge or sup-
ply air temperature.
WARNING
Improper installation, adjustment, alteration, ser-
vice or maintenance can cause personal injury, loss
of life, or damage to property.
Installation and service must be performed by a
qualified installer or service agency.
CAUTION
Physical contact with metal edges and corners
while applying excessive force or rapid motion can
result in personal injury. Use caution when working
near these areas during installation or while servic-
ing this equipment.
02/12
*2P0212*
KITS AND ACCESSORIES
506872−01
02/12
USED WITH SCC/SGC UNITS
Installation
1. Disconnect all electrical power to unit.
2. Open compressor section access doors.
3. Depending on the size of unit, perform step 4 or 5.
4. 036, 060, 120 Units: Position DDC hinged mounting
(WITH DIMPLES)
Figure 1. 036, 060, 120 Units − Installing DDC
Page 1
Danfoss RTC DDC KIT
WARNING
Electric shock hazard.
Can cause injury or death.
Before attempting to perform any
service or maintenance, turn the
electrical power to unit OFF at
disconnect switch(es).
Unit
may
supplies.
panel as shown in figure 1. Make sure the DDC faces
the A55 Prodigy control board. Align holes on hinged
bracket with dimples on the unit side. Secure DDC
panel to unit with two 5/8" screws.
UNIT SIDE
DDC HINGED
MOUNTING PANEL
SECURE DDC ASSEMBLY TO UNIT
WITH TWO 5/8" SCREWS
Hinged Mounting Panel